22
M414545
Figure 3
Solvent gases and vapors from dry 
cleaning machines create acids when 
drawn through the heater of a drying 
tumbler. These acids are corrosive to the 
drying tumbler as well as to the laundry 
load being dried. Be sure make-up air is 
free of solvent gases and vapors.
If the dry cleaning machines are in the  
same area as the tumbler, then the 
tumbler make-up air must come from a  
source free of solvent gases and  vapors.
W058
WARNING
To reduce the risk of fire and 
accumulation of combustible gases, DO 
NOT exhaust tumbler air into a window 
well, gas vent, chimney or enclosed, 
unventilated area such as an attic wall, 
ceiling, crawl space under a building, or 
concealed space of a building.
W059
WARNING
T108IE3C
NOTE: Inside of duct shall be
smooth. Do not use sheet
metal screws to join sections.
NOTE: Do not install wire
mesh or screen in this
opening as lint will build up
and prevent proper discharge
of air from drying tumblers.
ROOF 30" (76.2 CM)
ROOF 30" (76.2 cm)
CEILING
WALL
36 INCHES
(91.4 cm)
RECOMMENDED
SERVICE AREA
24 INCHES
(61.0 cm)
MINIMUM
PARTITION OR
BULKHEAD
REMOVABLE STRIP OF PANEL IN FRAMING WALL
TO PERMIT REMOVAL OF DRYING TUMBLER
FROM FRAMING WALL
CONSULT YOUR LOCAL BUILDING
CODE FOR REGULATIONS WHICH
MAY ALSO APPLY
T075IE3A
FOR BEST PERFORMANCE
provide an individual exhaust
duct for each drying tumbler. 
Do not install a hot water heater 
in room containing drying 
tumblers. It is better to 
have the water heater  in 
a separate room with a 
separate air inlet.
T108IE3A
TWO
DRYING
TUMBLERS
THREE
DRYING
TUMBLERS
ONE
DRYING
TUMBLER