APC mgetm galaxytm 6000 User Manual

Page of 46
Page 4 
- 6739381EN/JD
Characteristics
Characteristics common to all cubicles
MGE
TM 
Galaxy
TM
 6000 UPS: example of a rectifier-inverter cubicle
After moving them to their installation
location on their pallets,
MGE
TM 
Galaxy
TM
 6000 cubicles can be
moved short distances using a forklift or
pallet-mover when the front, rear and
side base panels are not mounted. The
forks can be inserted from all four sides
into 100 mm
+/– 10 mm high openings;
the unadjusted cubicle height (H) is
1900/2000 mm; after lifting the cubicle,
the height can be adjusted +/– 10 mm
by screwing in or out the four feet;
the bearing surface corresponds to
the area of the four cylindrical foot pads
(60 mm diameter) positioned in each
corner of the cubicle;
the cubicle depth (D) is 840 mm
(800 mm without doors and panels);
operating temperature range for
rectifier-inverter, frequency converter or
Static Switch Cubicles: 0°C to 35°C at
rated output (40°C for a maximum of
8 hours) and 30°C maximum for
overload conditions. Operation outside
the specified temperature range will
reduce service life;
relative humidity: 95% maximum;
maximum operating altitude without
derating: 1000 m;
connection via the bottom for
rectifier-inverter cubicles, or via the top
with the addtion of an optional duct that
can be installed on the right side of the
cubicle. The auxiliary and Static Switch
Cubicles are designed for connections
via the top or bottom.
the connection cables may be run in
three ways:
◗◗
in a trench running under the
cubicles,
◗◗
under a false floor,
◗◗
on the floor under the cubicles, in the
free space equal to the height of the
feet; in this case the cables should be
run side by side to avoid blocking the
flow of air for ventilation.
the intercubicle connection cables
are not supplied (except for the wires
for auxiliary interconnections);
normally the cubicles do not have to
be secured to the floor; the footpads
nevertheless have holes with an
average depth of 12 mm designed for
the fitting of M16 anchor bolts;
the cubicle doors are secured by
Ronis locks (key 405).
H
L
P
Galaxy 6000
www.m
geups.com
GALAX
Y 6000
   400 k
VA
SALLE
 IQ
Load p
rotecte
d
125 kV
A
120%
100%
50%
80%
0
0 Hour
 50 Min
.
100%
50%
0
Availa
ble Ba
ckup T
ime
Load l
evel
Norma
l AC
Bypas
s AC
Load
equipm
ent
Q1
Q5N
QF1
Q4S
Q3BP
15:24:
32   30
/05/200
5
Home
Alarms
Online
Trend
Statist
ics
Rectifie
r
Batter
y
Inverte
r
Bypas
s
Outpu
t
Set up