Alliance Laundry Systems 504523R3 User Manual

Page of 82
504523
25
• Dryer exhaust duct should enter the main duct at an 
angle of no more than 30
°
 pointing in the direction of 
the air flow. Ducts entering the main duct from 
opposite sides should be staggered so as not to oppose 
each other. See illustration below.
• Provisions should be made for periodic lint removal 
and cleaning of the main collector duct.
• The outside end of the main duct should have a 
weather hood (with hinged dampers) installed to 
prevent passage of weather elements, insects, dust, 
and dirt into the dryers.
• If a weather hood cannot be used, the outside end of 
the main duct should have a sweep elbow installed, 
and be directed downward as shown on page 24. If the 
main duct travels vertically through a roof rather than 
through a wall, install 180
°
 sweep elbow on the end 
of the duct with outlet at least 60.96 cm (24 inches) 
above the highest part of the building.
• Sufficient make-up air must be supplied to replace air 
exhausted from dryers.
NOTE: Where the exhaust duct pierces the wall or 
ceiling, an opening having a diameter of 10.2 cm 
(4 inches) larger than the diameter of the exhaust 
duct shall be provided, and the exhaust duct centered 
within the opening.
• Damper, Part No. 58786, should be installed in each 
dryer’s exhaust system. This will prevent a backdraft 
when dryer is not in use, and will keep the exhaust air 
in balance within the central exhaust system.
IMPORTANT: Provisions must be made for make-up 
air.
IMPORTANT: If several dryers are exhausted into a 
main collector duct, it is essential that ductwork be 
adequate in size and properly constructed for efficient 
operation.
DRYER EXHAUST DUCT
DRYER EXHAUST DUCT
DRYER EXHAUST DUCT
DRYER EXHAUST DUCT
AIR FLOW
MAIN COLLECTOR DUCT
30
°
30
°
30
°
D026IE3A
30
°
To reduce the risk of fire and the 
accumulation of combustion gases, DO NOT 
exhaust dryer air into a window well, gas 
vent, chimney or enclosed, unventilated 
area, such as an attic, wall, ceiling, crawl 
space under a building or concealed space 
of a building.
W045
WARNING