Alliance Laundry Systems hc165 User Manual

Page of 56
4
39
WARNING
The washer-extractor should be connected to an individual branch 
circuit not shared with lighting or other equipment.
Electrical Specifications HC60, IHC012, IHC060
60 liters / 12 pounds
Boiler Fed/Steam Heat
Electric Heat
Code
Voltage
Cycle
Phase
Wire
Full 
Load Amps
Recommended Circuit 
Breaker (US-market)
AWG/mm2
kW Standard
 
 Heating Elements
Full 
Load Amps
Recommended
 
 Circuit Breaker (US-
market)
AWG/mm2
US NON-US
US NON-US
N
440-480 50/60
3
3+PE
3
10
10
14/2.5
3x2 kW 
12
15
16
14/2.5
P
380-415 50/60
3
3+N+PE
7
15
16
14/2.5
16
20
20
12/4.0
Q
200-240 50/60
3
3+PE
7
15
16
14/2.5
23
30
32
10/6.0
X
200-240 50/60
1/3
2/3+PE
7
15
16
14/2.5
N/A N/A
N/A
N/A
Alternative Electric Heat Options
N
440-480 50/60
3
3+PE
3x1.4 kW
N/A N/A
N/A
N/A
P
380-415 50/60
3
3+N+PE
13
15
16
14/2.5
Q
200-240 50/60
3
3+PE
18
20
20
12/4.0
X
200-240 50/60
1/3
2/3+PE
N/A N/A
N/A
N/A
Table 2