PVI Industries Water Heater User Manual
PV500-33 05-2002
4
Section 33
DURAWATT EXR WATER HEATER
8. Open water outlet valve. Water heater is ready for operation. Heat up time will be dependent on
input and tank capacity.
9. After startup and with the water heater operating, allow the water in the tank to reach desired
temperature and the heating elements shut off. Draw hot water from a nearby outlet valve until
the heating elements energize. This will assure proper operation of the heating elements,
thermostat and other operating controls.
the heating elements energize. This will assure proper operation of the heating elements,
thermostat and other operating controls.
MAINTENANCE
1. A preventative maintenance program should be established to assure a long, trouble free life of
the water heater.
2. Flushing of the tank is recommended every two or three months, depending on water
conditions. To flush, disconnect (lockout) power to the unit. Open the drain valve and allow
water to flow through the tank until it runs clear. Close the drain valve. Draining two or three
gallons of water from the bottom of the tank on a weekly basis will also help prevent the
accumulation of sediment. A scale of lime will normally form on the heating elements and the
surface of the tank during heating cycles. The more hot water used, the more fresh water
containing the scale-forming elements are brought into the tank. As the temperature increases,
the rate of scale deposited will also increase. Sediment and scale accumulations in the tank will
greatly reduce the heating ability of the heater by reducing the effectiveness of the heat transfer
surfaces and can result in element failure.
water to flow through the tank until it runs clear. Close the drain valve. Draining two or three
gallons of water from the bottom of the tank on a weekly basis will also help prevent the
accumulation of sediment. A scale of lime will normally form on the heating elements and the
surface of the tank during heating cycles. The more hot water used, the more fresh water
containing the scale-forming elements are brought into the tank. As the temperature increases,
the rate of scale deposited will also increase. Sediment and scale accumulations in the tank will
greatly reduce the heating ability of the heater by reducing the effectiveness of the heat transfer
surfaces and can result in element failure.
3. Since PVI cannot control the use of the water heater, the water conditions or maintenance, the
warranty on the heating elements does not cover poor performance, structural failure or leaking
due to an excessive accumulation of scale.
due to an excessive accumulation of scale.
4. The temperature and pressure relief valve should be checked at regular intervals. Open and
close the valve to insure proper operation. If the valve does not open or close properly when
tested, it must be replaced. Replace the relief valve with a like kind or one meeting the
requirements stated on the rating decal located on the valve.
tested, it must be replaced. Replace the relief valve with a like kind or one meeting the
requirements stated on the rating decal located on the valve.
WARNING: THE RELIEF VALVE IS A SAFETY DEVICE. DO NOT PLUG VALVE.
5. All electrical connections must be checked two weeks after startup to assure tightness. Heating
and cooling from operation can loosen connections. Every month, connections should be
inspected for any discoloration of wire terminal points.
inspected for any discoloration of wire terminal points.
6. The contactors are sealed and require no periodic maintenance other than checking wire
connections. These contactors contain MERCURY and must be returned directly to the
manufacturer for proper disposal. To return contactors, please call WATLOW CUSTOMER
SERVICE
manufacturer for proper disposal. To return contactors, please call WATLOW CUSTOMER
SERVICE
@
507-454-5300 for a “Return Material Authorization” number. Mail the contactor
directly to the address provided by WATLOW CUSTOMER SERVICE for proper disposal.
Contact PVI
Contact PVI
@
800-433-5654 to purchase the new contactor. Please have the water heater serial
number when ordering replacement contactors and the printed rating of the contactor to be
replaced.
replaced.
7. Fuses for the load circuits are fast acting to prevent the contactor from rupturing in the event of
a heater short circuit. Replace with same type and rating.