INSTALLATION
WARNING/CAUTION
The gas used with this unit must be the type
specified on the spec plate on this unit. To
avoid personal injury or damage to the unit,
never use any other than the specified gas.
The heater and its gas connection must be leak
tested before placing the booster heater in
operation.
The booster heater and its individual shut-off
valve must be disconnected and isolated from
the gas supply piping system during any
pressure testing of the system at test
pressures in excess of 1/2 PSI (3.5 kPa.).
This appliance must be isolated from the gas
supply piping system by closing its individual
manual shutoff valve during any pressure
testing of the gas supply piping system at test
pressures equal to or less than 1/2 psig 
(3.5 kPa).
Dissipate test pressure from the gas supply
line before re-connecting the heater and its
manual shut-off cock to the gas supply line.
FAILURE TO FOLLOW THIS PROCEDURE MAY
DAMAGE THE GAS VALVE. OVER
PRESSURED GAS VALVES ARE NOT
COVERED BY THE WARRANTY.
The heater and its gas connections shall be
leak tested before placing the appliance in
operation. Use soapy water or commercially
available fluid for leak test. DO NOT use open
flame to test for leaks.
Incoming Gas Pressure Specifications
Operating Pressure Specifications at Manifold
The maximum inlet gas pressure must not exceed
the values shown above. The minimum gas
pressure listed is for the purposes of input
adjustment.
The manifold inside the heater is provided with a
pressure tap to measure the gas pressure. The
chart below lists the proper pressure amounts at the
manifold pressure tap when testing.
See Figure 6 for hook-up location and pressure tap
location.
Inches Water Column
Gas Type
Minimum
Maximum
Natural
5.0
10.5
Propane/LP
11.0
13.0
Inches Water Column At Pressure Tap
Gas Type
High Burn
Natural
3.5
Propane/LP
10.0