of Galaxy 3000 10-30 kVA ( N° 5103037500_BA) 
 
 
 
 
1 – Earth wiring between parallel units : 
 
In parallel mode it is necessary to connect each UPS with a supplementary earthing cable of following 
features : 
-
 
Equivalent section to the power supply cables  
-
 
Length as short as possible 
-
 
Not supplied with UPS 
 
Connected according to pictures below : 
UPS2
UPS1
Main earth
Earthing cable
Beetween UPS