Monessen Hearth dfx dbx24c User Manual

Page of 36
10
33D4047
DFX & DBX Series Vent Free Fireplaces
FIREPLACE INSTALLATION
Ensure that minimum clearances shown in Figures 5 and 6 are maintained. Left and right clearances 
are determined when facing the front of the firebox.
Follow these instructions carefully to ensure safe installation. Failure to follow these requirements 
may create a fire hazard.
Sidewall Clearances — The clearance from the inside of the appliance to any combustible adjacent 
wall should not be less than 9" for the DBX4C/DFX4C and DFX3C. Figure 5
Ceiling Clearance — The ceiling must be at least 4" from the top of the firebox opening. Figure 
5
Back Wall Clearance — The appliance may be placed against a combustible back wall.
Floor Clearance — The fireplace may be installed directly on a combustible floor or a raised platform 
of an appropriate height. Do not place fireplace on carpeting, vinyl, tile or other soft floor coverings. 
It may, however, be placed on flat wood, plywood, particle board or other hard surfaces. Be sure 
fireplace rests on a solid continuous floor or platform with appropriate framing for support and so 
that no cold air can enter from under the firebox. 
Mantel clearances — The canopy supplied with the unit must be installed. If a combustible mantel 
is installed. It must meet the clearance requirements detailed in Figure 6.
9"
Minimum
9"
Minimum
42" Minimum
FP2441
sidewall clg clear
FP441
Figure 5 - 
Sidewall and Ceiling Clearances
256O”
12”
10”
19”
FP2508
VFS DBX mantel clearances
Canopy
FP508
Figure 6 - 
Mantel Clearances
W
ARNING
The  dimensions  shown  in  Figures  5  and  6  are  minimum  clearances  to 
maintain in installing this heater. Left and right clearances are determined 
when facing the front of the heater. 
Follow these instructions carefully to ensure safe installation. Failure to 
follow instructions exactly can create a fire hazard.