APPLICATION
The T8602 Chronotherm® IV Programmable Thermostat 
provides electronic control of 24 Vac single-stage heating 
and cooling systems or 750 mV heating and 750 mV 
cooling. Refer to Table 1 for a general description of the 
thermostat. All T8602 Thermostats are powered by 
batteries.
MERCURY NOTICE
If this control is replacing a control that contains 
mercury in a sealed tube, do not place your old 
control in the trash. Dispose of properly.
Contact your local waste management authority 
for instructions regarding recycling and the 
proper disposal of the old control. 
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow 
the instructions can damage the product or cause 
a hazardous condition.
2. Check the ratings given in the instructions and on 
the product to make sure the product is suitable for 
your application.
3. Installer must be a trained, experienced service 
technician.
4. After completing installation, use these instructions 
to check out the product operation.
Location
Install the thermostat about 1.5m (5 ft) above the floor in 
an area with good air circulation at average temperature. 
See Fig. 1.
Do not install the thermostat where it can be affected by:
— drafts, or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall 
behind the thermostat.
Wallplate Installation
The thermostat can be mounted horizontally on the wall 
or on a 50.8 mm x 101.6 mm (2 in. x 4 in.) wiring box. 
Position wallplate horizontally on the wall or on a 
50.8 mm x 101.6 mm (2 in. x 4 in.) wiring box.
1. Position and level the wallplate (for appearance 
only). The thermostat will function properly even 
when not level. 
2. Use a pencil to mark the mounting holes. See Fig. 
2.
3. Remove the wallplate from the wall and drill two 
4.76 mm (3/16 in.) holes in the wall (if drywall) as 
marked. For firmer material such as plaster, drill 
two 5.56 mm (7/32 in.) holes. Gently tap anchors 
(provided) into the drilled holes until flush with the 
wall.
4. Position the wallplate over the holes, pulling wires 
through the wiring opening.
5. Loosely insert the mounting screws into the holes.
6. Tighten mounting screws.
Table 1. Description of T8602 Thermostats.
T8602
System
Changeover
System
Selection
Fan
Selection
Comments
D
Heat-Cool
Manual or 
Automatic 
Selectable
Heat-Off-Cool or
Heat-Off-Cool-Auto
On-Auto
System and fan selections are done 
by keyboard.