Honeywell v4055 User Manual

Page of 8
V4055A,B,D,E ON-OFF FLUID POWER GAS VALVE ACTUATOR
5
60-2309—1
3
IMPORTANT
1. All wiring must comply with all applicable electrical 
codes, ordinances, and regulations. All wiring must 
be NEC Class 1.
2. Voltage and frequency of the power supply connected 
to this control must agree with those marked on the 
device.
3. Loads connected to the Auxiliary Switch and/or Proof-
of-Closure Switch, if used, must not exceed the rat-
ings given in the Specifications section.
Install Valve
The actuator is mounted directly on the valve bonnet after the 
valve is installed in the gas supply line. Refer to the instructions 
packed with the gas valve for installation details. When 
installing the gas valve, make sure:
1. Sufficient clearance is left to install and service the actuator.
2. Ambient temperatures at the valve location do not 
exceed actuator ratings. See Specifications section.
3. Position of the valve permits hookup to the damper if one 
is controlled.
Install Accessory Switches (If 
Needed)
An spdt switch can be installed to operate an auxiliary load up 
to 1/2 hp (0.37 kW). See Table 5. The switch can be adjusted 
to operate at any point in the valve stroke.
A Proof-of-Closure Switch can also be installed with a V5055/
V5097C or E Valve (with double seal) on any V4055 Actuator 
to provide a valve seal overtravel interlock. The spdt 
Proof-of-Closure Switch is installed to make or break a circuit 
when the valve is in the closed position. The switch is not 
adjustable.
NOTE: Mark the actuator or valve to indicate any changes 
made.
To install the switches:
1. Remove the actuator faceplate (two screws).
2. Remove the silver-colored barrier to expose the actuator 
stem.
3. Insert the Auxiliary Switch in the position indicated in Fig. 
2. Fasten with two screws through the actuator base.
4. Insert the Proof-of-Closure Switch in the position shown 
in Fig. 2. The switch mounts against the side of the 
actuator housing. The mounting holes are spaced to 
assure mounting the switch in the correct position. 
Fasten with two screws through the actuator base. (The 
Proof-of-Closure Switch is not adjustable.)
5. If only one switch is used, install the narrow barrier 
included with the switch in the unused space.
6. Mount the actuator before making wiring connections 
and adjustments to the Auxiliary Switch.
Mount Actuator on Valve
1. Check the final position of the valve body to be sure that 
the actuator is in the proper position when mounted on 
the valve. This is especially important when the actuator 
is used to drive a damper.
2. If two smaller sized valves are mounted very closely 
together, as in an Industrial Risk Insurers approved type 
of valve train, it may be necessary to mount the 
actuators off center to provide adequate clearance.
Fig. 2. V4055 Actuator with cover removed.
3. Slip the bottom collar of the actuator over the 
valve bonnet assembly. Rotate the actuator to the 
desired position and use a 5/32 in. Allen wrench to 
securely tighten the two setscrews to 50 to 60 lb-in. 
(5.7 to 6.8 N•m). 
4. Connect the damper linkage, if used. Refer to the 
instructions packed with the damper arm.
Mount and Adjust 7616BR 
Damper Crank Arm (If Used)
IMPORTANT
When a damper crank arm is used with a NEMA 4 
actuator that is exposed to ice or sleet, a suitable 
shield must be installed to prevent ice or sleet 
buildup.
Follow installation and adjustment directions included with 
damper crank arm. Maximum pushrod travel is 2-5/16 in.
(59 mm) through a stroke of 52 degrees. See Fig. 3.
133568
AUXILIARY
SWITCH
133569
VALVE-
CLOSED
INDICATION
SWITCH
EACH SWITCH SECURED BY
TWO SCREWS FROM UNDERSIDE OF BASE.
ADJUSTING 
SCREW FOR 
AUXILIARY 
SWITCH
IF ONLY ONE SWITCH IS USED, INSTALL BARRIER
IN OPEN POSITION.
M7326B