Wiring
CAUTION
Can Cause Electrical Shock or Equipment Damage.
Disconnect power supply before connecting wiring. 
Disconnect the power supply before connecting wiring to 
prevent electrical shock and equipment damage. All wiring 
must comply with applicable local codes and ordinances. 
Refer to Fig. 13 and the wiring diagrams furnished with the 
system equipment to complete the wiring.
Fig. 13. T6031H switch terminal arrangement and 
switching. 
W7459A,C AND W7212 Solid State 
Economizer Logic Module
Location and Mounting W7459 Economizer 
Logic Module 
Mount the W7459 Economizer Logic Module on the side of the 
M7415 or M8405 Damper Actuator. When planning the 
installation, allow enough clearance for maintenance and 
service. Install the W7459 Economizer Logic Module where it 
is protected from rain and snow. One mounting screw is 
supplied to secure the W7459 to the actuator (after the 
actuator is mounted). See Fig. 14.
Location and Mounting W7212
The logic modules mount on an M7215 or a sheet metal duct 
or panel. When planning the installation, allow enough 
clearance for maintenance and service (see Fig. 15 and 16 for 
dimensions). Mount device in a location protected from rain, 
snow and direct sunlight. Secure device to sheet metal using 
the two supplied mounting screws.
CAUTION
Equipment Damage Hazard.
Mounting screws longer than 5/8 in. can damage
internal motor components.
When mounting the module to an M7215 use only the 
included #6 5/8 in. thread-forming screw.
Fig. 14. Mounting W7459 on M7415 or M8405 Damper 
Actuator.
Fig. 15. Direct mounting of module.
SETPOINT
FOR T6031H
SETPOINT
SWITCH 
DIFFERENTIAL
TEMPERATURE
RISE
R AND W LOCATIONS 
DEPEND ON MODEL 
AND CONSTRUCTION
W
B
R
BREAKS R-B;
MAKES R-W
ON RISE
MAKES R-B;
BREAKS R-W
ON FALL
M9089
M9091
W7459 
ECONOMIZER PACKAGE
M7415, M7405 OR 
M8405 ACTUATOR
M20717B 
5/8 INCH SCREW INCLUDED WITH LOGIC MODULE. 
M7215 DAMPER MOTOR 
ECONOMIZER