SOLID STATE ECONOMIZER SYSTEM
63-2484—2
16
The setpoint scale markings, located on the W7459, are A,B,C 
and D. Turn the setpoint potentiometer fully clockwise to the D 
setting. The economizer selects the air that has lower enthalpy 
or temperature for cooling; for example, if outdoor air has lower 
enthalpy or temperature than return air, the outdoor air damper 
is opened to bring in outdoor air for free cooling. 
Remote Minimum Position Control
Remote control of outdoor air dampers is desirable when 
requiring temporary additional ventilation. The addition of a 
S963B1128 Remote Potentiometer allows occupants to open 
or close the dampers beyond minimum position for modified 
ventilation.
SEQUENCE OF OPERATION
Economizer Sequence of Operation
(WITH AND WITHOUT DIFFERENTIAL ENTHALPY) 
The economizer operating sequence for both the modulating 
and the three-position control systems are identical when the 
outdoor enthalpy temperature is above the mixed air setpoint 
of 55°F (13°C). The operating sequence for both, using a 
standard two-stage thermostat is: 
1. The first stage of the thermostat signals a need for
cooling.
2. The W7459 Solid State Economizer Logic Module
begins to make decisions regarding the unit/
economizer operation.
3.
a. On the standard (non-differential) economizers, the 
logic module checks the outdoor air C7400 Enthalpy 
Sensor or C7650 Temperature Sensor to determine if 
the enthalpy or temperature is below the setpoint. 
b. On the differential economizers, the logic module 
checks to determine if the outdoor air temperature is 
below the return air temperature. 
4. If the logic module uses the outside air for cooling, the 
mixed air sensor prevents the entering air from going 
below 50°F (10°C).
a. On the modulating system, the control closes the 
outside air damper and opens the return air damper 
to mix the outside air and return air to maintain 50°–
55°F (10°–13°C).
b. On the three-position system, the mixed air sensor 
switch opens, closing the fresh air damper until the 
mixed air sensor temperature returns above 55°F 
(13°C), closing the switch and re-opening the outside 
air damper.
5.
a. If the logic module senses that the outside air is not 
suitable for cooling, the air conditioning unit com-
pressor is energized and the space is cooled with 
refrigerated air.
b. On the two-stage thermostat, the economizer is the 
first stage if the outside air temperature is suitable for 
cooling. The compressor on the unit is energized if 
the second stage of the thermostat is energized, 
thereby creating an integrated economizer.
6. Refer to Table 4 for further information on outside air 
damper positions.
1
Standard economizer position based on enthalpy control set on the A setting and 50% relative humidity.
2
Closed position is either the minimum position or fully closed, depending on the job setting.
3
Opening/closing is dependent on the mixed air temperature.
Table 4. Outdoor air damper positions.
Outside 
Temperature
1
Standard Economizer Damper Position
Return 
Temperature
1
Differential Enthalpy Damper Position
Modulating
2
3-Position
2
Modulating
2,3 
3-Position
2,3
80
Closed
Closed
80
Closed
Closed
85
Open
Open
75
Closed
Closed
75
Closed
Closed
80
Open
Open
70
Open
Open
75
Open
Open
65
Open
Open
60
Open
Open
75
Open
Open
55
Open
Open
75
Open
Open
54 and down
Modulating
Opening/Closing
75
Modulating
Opening/Closing