Honeywell m7415 User Manual

Page of 32
SOLID STATE ECONOMIZER SYSTEM
19
63-2484—2
7. If all minimum and maximum position adjustments are 
complete, remove the T-T1 jumper and reconnect the 
mixed air sensor.
EQUATION 1. FORMULA TO AID MINIMUM POSITION ADJUSTMENT.
(T
O
 × OA)+(T
R
 × RA)= T
M
Where:
T
O
 = Outdoor air temperature
OA = Percent of outdoor air
T
R
 = Return air temperature
RA = Percent of return air
T
M
 = Resulting mixed air temperature
NOTE: The following sample calculation uses only Fahren-
heit temperature.
EXAMPLE: Assume local codes require 10% outdoor air dur-
ing occupied conditions, outdoor air is 60°F and 
return air is 75°F. Under these conditions, what is 
the temperature of the mixed air?
(0.1 × 60°F)+(0.9 × 75°F)=6.0°F + 67.5°F=73.5°F
Mixed air will be 73.5°F when OA is 60°F and RA is 75°F with 
10 percent outdoor air entering the building.
DCV Maximum Position Adjustment
1. Disconnect mixed air sensor from terminals T and T1 
and short terminals T and T1.
2. Connect a jumper between terminals AQ and AQ1.
3. Connect 24 Vac across terminals TR and TR1.
4. Adjust the potentiometer on the face of the device with a 
small screwdriver for desired maximum position.
5. If all minimum and maximum position adjustments are 
complete, remove the T-T1 jumper and reconnect the 
mixed air sensor.
Enthalpy Changeover Setpoint
Outdoor Enthalpy Changeover Setpoint
(Single Enthalpy)
The outdoor enthalpy changeover setpoint returns the outdoor 
air damper to minimum position when enthalpy rises above its 
setpoint. Enthalpy setpoint scale markings, located in the 
device, are A, B, C and D. See Fig. 18 for the corresponding 
control point. The factory-installed 620-ohm jumper must be in 
place across terminals SR and SR+. Temperature and humidity 
points to the left of the selected curve will allow the dampers to 
open for free cooling.
Differential Enthalpy Changeover Setting
Differential enthalpy control uses two C7400 Enthalpy Sensors 
connected to one logic module. The logic module compares 
outdoor air to return air.
NOTE: Turn the enthalpy setpoint potentiometer fully clock-
wise to the D setting.
The logic module selects the lower enthalpy air (return or 
outdoor) for cooling. For example, when outdoor air has lower 
enthalpy than return air, the module calls to open the outdoor 
air damper to bring in outdoor air for free cooling.
Exhaust Setpoint
The exhaust setpoint determines when the exhaust fan runs 
based on damper position. When the exhaust fan call is made, 
the module provides a 60 ±30 second delay before exhaust fan 
activation. This delay allows the damper to reach the 
appropriate position to avoid unnecessary fan overload.
NOTES:
EF and EF1 are 24V dry contacts only. An external 
line voltage contactor is required to operate the 
exhaust fan.
When the exhaust fan is deactivated the EF and 
EF1 contacts open immediately.
CHECKOUT AND TROUBLESHOOTING
Tables 6 through 10 provide step-by-step economizer checkout 
and troubleshooting steps. See Fig. 23 and 25 for enthalpy 
setpoint potentiometer, minimum position potentiometer and 
LED locations.
Fig. 26. Meter location for checkout and troubleshooting.
1
1
2
2
M9097
ENTHALPY CHANGEOVER
SETPOINT
LED LIGHTS WHEN
OUTDOOR AIR IS SUITABLE 
FOR FREE COOLING
INSERT DC MILLIAMMETER BETWEEN SO AND S FOR CHECKOUT 
AND TROUBLESHOOTING.
JUMPER USED FOR SINGLE ENTHALPY CONTROL.
TR
TR1
A
B
C
D
SO
SR
+
+
+
C7400
620 OHM
JUMPER
DC 
MILLIAMMETER
W7459
S
+