Set Up and Calibration Procedures 
Set Up Groups 
34 
  HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 
Revision 7 
  
 
7/08 
Set Up Groups 
Pressing the SET UP key on the keypad provides access to the various set up groups and allows you to set 
up operating parameters, (such as input types and alarms), calibrate the actuator’s inputs and outputs, set 
communications, and check actuator status. Table 8 on the next page lists the set up groups that are 
available by using the SET UP and FUNCTION keys on the keypad. 
 
Table 8 Set Up Groups 
 
Set Up Group Title 
Pressing the FUNCTION Key Allows You to… 
For Details, See 
SET 
INPUT 
 
Select and set various parameters associated with the 
input signal to the actuator.  
Table 10 
SET 
RELAYn 
n
 = 1, 2, 3, or 4 
Select relay functions.  NOTE:  Set Relay groups will 
show on display only if relays are installed in the 
actuator.  
Table 13 
SET 
CUROUT 
 
Select the output signal type of the actuator. 
Table 15 
SET 
COMM 
 
Select communication parameters for remote control of 
actuator when connected to a SCADA system. 
Table 16 
SET 
DIGINP 
 
Select the parameters for external digital input states.   
Table 17 
SET 
DISPLA 
 
Select and set parameters for the local display.  
Table 18 
CAL 
INPUT 
 
Calibrate input zero and span values.  
 
Calibration 
Procedure,  
Table 25 
CAL 
MOTOR 
 
Calibrate zero and span values for motor operation. 
ATTENTION
 
When calibrating the motor to a short stroke range, 
you must reset the end-of-travel limit switches.  See 
Setting End-of-Travel Limit Switches.
   
Calibration 
Procedure,  
Table 26 
CAL 
CURENT 
 
Calibrate actuator output. 
Calibration 
Procedure,  
Table 27 
SET 
LOCK 
 
Set or change security password.  Enable or disable 
security access to set up parameters and calibration 
set up.   
Table 19 
READ 
STATUS 
 
Display operating and alarm status. Display self-test 
diagnostic results.   
Table 20 
SET 
DRVINF 
Display and/or set various parameters specific to the 
actuator.   
Table 21