Honeywell herculine 2000 User Manual

Page of 128
Set Up and Calibration Procedures 
Drive Set Up Group 
56 
  HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 
Revision 7 
  
 
7/08 
Drive Set Up Group 
Table 21 lists the parameters and selections available for the SET DRVINF group. 
Table 21 Drive Set Up Group Parameters 
Actuator Lower 
Display 
Prompt 
Selections or 
Range of Setting  
Parameter Definition/PDA HercuLink
®
 Prompt 
VERSON 
nnnn 
FIRMWARE VERSION
 Read Only.  Displays the firmware 
version currently in use by the actuator’s CPU.   
SPEED 
(150
° @ 60hz) 
  6 S 
12 S 
25 S               
50 S               
75 S 
STROKE SPEED
 Read Only.  The speed is the number of 
seconds it takes for the actuator shaft to move its full range 
of travel.  
SPEED 
(90
° @ 60hz) 
  3.2 S 
  7.2 S 
15 S               
30 S               
45 S 
STROKE SPEED
 Read Only.  The speed is the number of 
seconds it takes for the actuator shaft to move its full range 
of travel.  
SPEED 
(150
° @ 50hz) 
  7.5 S 
  15 S 
30 S               
60 S               
90 S 
STROKE SPEED
 Read Only.  The speed is the number of 
seconds it takes for the actuator shaft to move its full range 
of travel.  
SPEED 
(90
° @ 50hz) 
  4.5 S 
  9 S 
18 S               
36 S               
54 S 
STROKE SPEED
 Read Only.  The speed is the number of 
seconds it takes for the actuator shaft to move its full range 
of travel.  
POWER 
 
 
 
1206 
1205 
2206 
2205 
POWER INPUT VOLTAGE AND FREQUENCY
 Read 
Only.
  Selects the power input voltage and line frequency of 
the actuator.      
1206
— 120Volts, 60Hz 
1205
— 120Volts, 50Hz 
2206
— 220Volts, 60Hz 
2205
— 220Volts, 50Hz 
ROTATE 
 
 
90 
150 
ROTATION
— Indicates the factory calibrated degrees of 
rotation. 
90
— Factory calibrated for 90 degrees of rotation. 
150
— Factory calibrated for 150 degrees of rotation. 
TAG 
nnnnnn 
TAG NAME
— Selects the tag name or identifier of the 
actuator.  Up to 6 alphanumeric characters.  See “Set Tag 
Nam
e” on next page. 
DMFG 
mmddyy  * 
or 
ddmmyy 
MANUFACTURING DATE
 Read Only.  Displays date 
code of manufacture for actuator.