Set Up and Calibration Procedures 
Auto - Manual Drive Switch 
64 
  HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 
Revision 7 
  
 
7/08 
Auto - Manual Drive Switch 
The Auto - Manual switch is located on the side of the actuator case below the handwheel.  The switch 
allows manual mode control of the actuator motor for set up, calibration and troubleshooting.   
Figure 24 shows an illustration of the Auto - Manual switch and Table 24 describes the switch settings.  
The Auto - Manual Drive switch setting overrides all input signals (analog signal and remote setpoint) and 
local display mode settings. When not in auto the manual LED will flash every second. 
 
MANUAL
OFF
CW
CCW
OFF
A
U
T
O
AUTO - MANUAL DRIVE
 
 
Figure 24 Auto - Manual Switch 
 
 
 
Table 24 Auto - Manual Switch Functions 
 
Switch Setting 
Motor Drive Control 
AUTO 
Actuator moves according to signal input and set up configuration.  
CCW 
Actuator moves to the fully counterclockwise position.   
CW 
Actuator moves to the fully clockwise position. 
OFF 