Set Up and Calibration Procedures 
Calibration 
68 
  HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 
Revision 7 
  
 
7/08 
Jumper W2
 
Figure 27  Jumper Location on CPU PWA 
 
Calibrate Input 
The HercuLine
®
 2001/2002 actuator accepts a variety of signal inputs. 
1.  0 to 20 mA, or 4 to 20 mA 
2.  0 to 5 Volts,1 to 5 Volts, or 0 to 10 Volts 
The input type is selected through the Input set up group using the local keypad.   
Refer to Figure 25 for the wiring connections and follow the procedure in Table 25 to calibrate the input 
circuit of the HercuLine
®
 2001/2002 actuator.   
 
 
ATTENTION 
For an input calibration to be saved, you must complete the procedure.  The calibration will not 
be saved if you exit without completing the steps of the procedure.   
To exit calibation mode, press DISPLAY or SETUP keys.