Design Dynamics VTD-18N-JHB User Manual

Page of 16
www.desatech.com
114370-01E
8
INSTALLATION
Continued 
CHECKING GAS CONNECTIONS
 WARNING: Test all gas piping 
and  connections,  internal  and 
external to unit, for leaks after 
installing or servicing. Correct 
all leaks at once.
  WARNING:  Never  use  an 
open flame to check for a leak. 
Apply a noncorrosive leak detec-
tion fluid to all joints. Bubbles 
forming show a leak. Correct all 
leaks at once.
PRESSURE TESTING GAS SUPPLY 
PIPING SYSTEM 
Test Pressures In Excess Of 1/2 PSIG 
(3.5 kPa)
1.  Disconnect  log  set  with  its  individual 
equipment.shutoff.valve.from.gas.supply.
piping.system.
2.  Cap off open end of gas pipe where equip-
ment shutoff valve was connected.
3.  Pressurize supply piping system by either 
using.compressed.air.or.opening.main.gas.
valve.located.on.or.near.gas.meter.
4.  Check all joints of gas supply piping sys-
tem..Apply. noncorrosive. leak. detection.
fluid to gas joints. Bubbles forming show 
a.leak..
5.. Correct.all.leaks.at.once.
6.. Reconnect.log.set.and.equipment.shutoff.
valve.to.gas.supply..Check.reconnected.
fittings for leaks. 
Test Pressures Equal To or Less Than 
1/2 PSIG (3.5 kPa)
1.. Close.equipment.shutoff.valve.(see.Fig-
ure 5).
2.  Pressurize supply piping system by either 
using.compressed.air.or.opening.main.gas.
valve.located.on.or.near.gas.meter.
Figure 6 - Checking Gas Joints 
HEARTH KIT ASSEMBLY AND 
INSTALLATION
1.  Determine which side the gas line will be 
coming into the fireplace. 
.
NOTICE: Unit comes preassembled with 
gas inlet on right side. If your fireplace gas 
supply is on the left, gas inlet should be 
repositioned.to.left.side.of.unit.
2.  If gas supply line in your fireplace is on the 
right side, continue to step 3. If not, see 
Repositioning the Gas Inlet to the Left Side 
of Unit
, page 9.
3.  Install adapter fitting that comes with log 
set  into  fireplace  gas  supply  pipe  (see 
Figure  7). Seal using thread sealant.
Figure 7 - Connecting Adapter to Gas 
Supply
Gas.
Connector.
Tube
Adapter.
Fitting
Gas.Inlet.
Fitting
Equipment.Shutoff.Valve
Gas.Meter
Figure 5 - Equipment Shutoff Valve
Equipment.
Shutoff.
Valve
Open
Closed
3.  Check all joints from gas meter to equip-
ment shutoff valve (see Figure 6). Apply 
noncorrosive  leak  detection  fluid  to  all 
joints. Bubbles forming show a leak. 
4.. Correct.all.leaks.at.once.