Dodge en221 User Manual

Page of 16
 
 
Dodge Engineering & Controls, Inc. 
Toll Free (877) 334-2875  Fax: (978) 244-1422 
 
Installation
 
EN221 and EN310 Non-Spring Return Electronic Actuators 
EA0662R1
a
f
d
g
c
e
b
PUSH
 
 
Figure 1.  Parts of the EN221 and EN310 Actuators. 
a. Actuator 
b.  U-bolt shaft adapter 
c. Position 
indicator 
d.  Shaft adapter locking 
clip 
e. Position 
indicator 
adapter 
f. Mounting 
bracket 
g. Mounting 
screws 
 
Product Description 
This installation instruction describes the steps for 
direct-coupled mounting of the EN221 and EN310 
series non-spring return (NSR) electronic actuators.  
Product Numbers 
EN221x 
EN310x 
Installation Conventions 
WARNING: 
 
Personal injury or loss of life may 
occur if you do not follow the 
procedures as specified. 
CAUTION: 
 
Equipment damage or loss of 
data may occur if you do not 
follow procedure as specified. 
CLOCKWISE
COUNTER CLOCKWISE
EA0320R2
 
Required Tools 
•  10 mm (13/32-inch) open-end wrench 
•  Drill 
4 mm (5/32-inch) drill bit  
•  Phillips screwdriver 
•  Marker or pencil 
•  Adjustable pliers 
Expected Installation Time 
30 minutes 
Prerequisite 
The actuator is shipped from the factory with a 5° 
pre-load to ensure tight close-off of the damper. To 
release the pre-load, press the PUSH button before 
mounting the actuator. 
Installation 
 
WARNING: 
Do not open the actuator.  
NOTE: 
You must place the actuator on the 
damper shaft so that the front of the 
actuator is accessible. The label and the 
manual override button are on the front 
side.  
1.  Place the actuator on the damper shaft with the 
front of the actuator accessible. The label and 
the manual override button are on the front side.  
2.  For the EN221B2x and EN310B2x only: 
Determine the rotation of the damper shaft. Set 
the direction of rotation arrow to match the 
rotation.  
 
Figure 2.  Direction of Rotation Switch. 
3.  For all models: See Figure 3 and Figure 4 for 
clockwise-to-open (CW) installation. See Figure 
5 and Figure 6 for co
unterclockwise-to-open 
(CCW) installation. 
UL Doc. No. 129-272 
EAI/EN-1 
Dodge Engineering & Controls, Inc. 
Rev. 5, Jan., 2005