Honeywell RTH7500D User Manual

Page of 64
69-1730
60
Cannot set 
System setting 
to Cool.
Check Installer Setup Number 0170, 
Heating and/or Cooling System Type; make 
sure the setting matches the installed 
heating and/or cooling system.
“Heat On” is 
not shown in 
the display.
Set the System setting to Heat and set the 
temperature setting above the room 
temperature. If “Heat On” is shown solidly in 
the display, but the heating system does not 
turn on, see “Heating system does not turn 
on” in the Troubleshooting Tips.
“Cool On” is 
not shown in 
the display.
Set the System setting to Cool and set the 
temperature setting below the room 
temperature. If “Cool On” is shown solidly in 
the display, but the cooling system does not 
turn on, see “Cooling system does not turn 
on” in the Troubleshooting Tips.
“Wait” shows in 
the display.
Compressor minimum-off timer is active. 
Wait up to five minutes for the cooling or 
heating system to turn on.
Fan does not 
turn on in a call 
for heat 
(electric fur-
naces only).
Check Installer Setup Number 0180, Fan 
Control in Heating, and make sure it is set 
to Electric Heat.
Heat pump 
puts out cool 
air in the heat 
mode and 
warm air in the 
cool mode 
(heat pumps 
only).
Check Installer Setup Number 0190, Heat 
Pump Changeover Valve, and make sure 
the setting matches the changeover 
required by the installed heat pump.
Troubleshooting Tips (Cont)
If . . .
Then . . .
69-1730.fm  Page 60  Tuesday, July 13, 2004  12:45 PM