Table 5. TP974A, TP978A-E, TP979A-E Thermostat Specifications.
Old
Model No.
New
Model No.
Action
Setpoint
Supply Air
Pressure
psi (kPa)
psi (kPa)
Degrees
Throttling
Range
Special Features
TP974A 1000
TP974A 2000
DA, 1- or
2-Pipe Sensor
Bleed Type
Bleed Type
50-100
°
F
(10-38
°
C)
Range
18 (124)
3-15 (21-103)
Output
—
Sensor for use with
RP908 & RP920
Controller
RP908 & RP920
Controller
TP978A 1006
No
Replacement
DA Heating
DA Cooling
DA Cooling
60-73
°
F
Heating
18 (124)
2-10
°
F
(1.1-5.6
°
C)
ZEB Energy
Conservation, Setpoint
Stop 73
Conservation, Setpoint
Stop 73
°
F (Heating),
77
°
F (Cooling)
TP978B 1004
No
Replacement
RA heating
DA Cooling
DA Cooling
77-90
°
F
Cooling
TP978C 1002
No
Replacement
DA Heating
RA Cooling
RA Cooling
TP978D 1000
No
Replacement
RA Heating
RA Cooling
RA Cooling
TP978E 1007
TP978E 2007
RA (Right Side)
DA (Left Side)
68-82
°
F
0.18 (1)
1-4
°
F
Includes Cover
Special System-
Powered Thermostat
for Carrier
Special System-
Powered Thermostat
for Carrier
TP979A 1005
TP979A 2005
DA Heating
DA Cooling
DA Cooling
60-90
°
F
18 (124)
Adjustable
2-10
°
F
(1.1-5.6
°
C)
—
TP979B 1003
TP979B 2003
RA Heating
RA Cooling
RA Cooling
—
TP979C 1001
TP979C 2001
DA Heating or
Cooling
RA Heating or
Cooling
RA Heating or
Cooling
—
TP979D 1009
TP979D 2009
DA Heating
DA Cooling
13 (90) Day
18 (124) Nite
Day/Nite Heat with
night set down; Cool
with night set up.
night set down; Cool
with night set up.
TP979E 1006
TP979E 2006
DA Heating
RA Cooling
RA Cooling