Moxa ioLogik E2212 Specification Guide
1
w w w. m o x a . c o m
i n f o @ m o x a . c o m
Industrial I/O
Active Ethernet I/O with 8 digital inputs, 8 digital outputs,
and 4 configurable DIO
ioLogik E2212
Selectable digital I/O combination (by software)
›
Accepts PNP or NPN sensors
›
DI counter saved automatically when power shuts off
›
Instant event messaging by TCP/UDP/email/SNMP trap
›
Easy-to-use Click&Go™ Logic for local output control
›
PC-based configuration utility and web console
›
I/O control over Modbus/TCP and SNMP protocol
›
Windows/WinCE VB/VC.NET and Linux C APIs
›
Peer-to-Peer I/O without controller
›
Introduction
Flexible Digital Input/Output Configuration
The ioLogik E2212 provides system integrators with the flexibility to
handle various field demands with channels that can be configured
by software for input or output operation. You can configure the I/O
channels to suit your needs, for combinations such as 12-inputs/8-
outputs, 8-inputs/12-outputs, or 10-inputs/10-outputs.
handle various field demands with channels that can be configured
by software for input or output operation. You can configure the I/O
channels to suit your needs, for combinations such as 12-inputs/8-
outputs, 8-inputs/12-outputs, or 10-inputs/10-outputs.
Single Ethernet DIO that Accepts 3 Sensor Types
Unlike traditional Ethernet I/O products, the ioLogik E2212 can connect
to dry contact, PNP, and NPN sensors at the same time. You can
choose the sensor type based on your wiring approach.
to dry contact, PNP, and NPN sensors at the same time. You can
choose the sensor type based on your wiring approach.
Specifications
LAN
Ethernet: 1 x 10/100 Mbps, RJ45
Protection: 1.5 KV magnetic isolation
Protocols: Modbus/TCP, TCP/IP, UDP, DHCP, Bootp, SNMP (MIB for
I/O and Network), HTTP, CGI, SNTP
Protection: 1.5 KV magnetic isolation
Protocols: Modbus/TCP, TCP/IP, UDP, DHCP, Bootp, SNMP (MIB for
I/O and Network), HTTP, CGI, SNTP
Serial Communication
Interface: RS-485-2w: Data+, Data-, GND
Serial Line Protection: 15 KV ESD for all signals
Serial Line Protection: 15 KV ESD for all signals
Serial Communication Parameters
Parity: None
Data Bits: 8
Stop Bits: 1
Flow Control: None
Baudrate: 1200 to 115200 bps
Protocol: Modbus/RTU
Data Bits: 8
Stop Bits: 1
Flow Control: None
Baudrate: 1200 to 115200 bps
Protocol: Modbus/RTU
Digital Input
Channels: 8, source/sink selectable
Sensor Type: 2 6-point groups for NPN/PNP type
I/O Mode: DI or Event Counter (up to 900 Hz)
Dry Contact:
• Logic 0: short to GND
• Logic 1: open
Wet Contact: (For Source Type)
• Logic 0: 0 to 3 VDC
• Logic 1: 10 to 30 VDC (DI COM to DI)
Sensor Type: 2 6-point groups for NPN/PNP type
I/O Mode: DI or Event Counter (up to 900 Hz)
Dry Contact:
• Logic 0: short to GND
• Logic 1: open
Wet Contact: (For Source Type)
• Logic 0: 0 to 3 VDC
• Logic 1: 10 to 30 VDC (DI COM to DI)
Common Type: 6 points per COM
Isolation: 3K VDC or 2K Vrms
Counter/Frequency: 900 Hz, power off storage
Digital Filtering Time Interval: Software selectable
Over-voltage Protection: 36 VDC
Poweroff Counter Memory: 48 bytes
Isolation: 3K VDC or 2K Vrms
Counter/Frequency: 900 Hz, power off storage
Digital Filtering Time Interval: Software selectable
Over-voltage Protection: 36 VDC
Poweroff Counter Memory: 48 bytes
Digital Output
Channels: 8, sink type, 36 VDC, 200 mA
I/O Mode: DO or Pulse Output (up to 100 Hz)
Pulse Wave Width/Frequency: 10 ms/100 Hz
Over-voltage Protection: 45 VDC
Over-current Limit: 400 mA (typical)
Over-temperature Shutdown: 175°C (min.)
Output Current Rating: Max. 200 mA per channel
Isolation: 2K Vrms or 3K VDC (Magnetic)
I/O Mode: DO or Pulse Output (up to 100 Hz)
Pulse Wave Width/Frequency: 10 ms/100 Hz
Over-voltage Protection: 45 VDC
Over-current Limit: 400 mA (typical)
Over-temperature Shutdown: 175°C (min.)
Output Current Rating: Max. 200 mA per channel
Isolation: 2K Vrms or 3K VDC (Magnetic)
DI/DO Configurable Channels
Channels: 4
I/O Mode:
• DI or Event Counter (up to 900 Hz)
• DO or Pulse Output (up to 100 Hz)
I/O Mode:
• DI or Event Counter (up to 900 Hz)
• DO or Pulse Output (up to 100 Hz)
Power Requirements
Power Input: 24 VDC nominal, 12 to 48 VDC
Power Consumption: 282 mA typical @ 24 VDC