3.5 UPS Initial Startup 
To start up the UPS: 
1. Verify that the internal batteries are connected. If optional EBMs are 
installed, verify that the EBMs are connected to the UPS. 
 
2. Plug the equipment to be protected onto the UPS, but do not turn on the 
protected equipment. 
 
3. Plug in the UPS input power cord. The UPS front panel display illuminates 
and UPS status display shows “STbY” 
 
4. Press and hold the button 
  more than 3 seconds. The UPS status 
display changes to “NORM” 
 
6. Check the UPS display for active alarms or notices. Resolve any active 
alarms before continuing. See “Troubleshooting” 
 
8. If optional EBMs are installed, see “Configuring UPS for EBM numbers” on 
page 21 to set the number of installed EBMs. 
 
9. To change any other factory-set defaults, see “Operation” 
 
Note: At initial startup, the UPS sets system frequency according to input line 
frequency.