APC MGE Galaxy 5000 SUG580S90UL User Manual

Product codes
SUG580S90UL
Page of 22
Output Contacts
A.General alarm
B.Battery fault
C.Load on UPS
D.Load on automatic bypass
E. Load on battery power
F. Low battery warning
EPO Options
An optional Emergency Power Off or Remote Emergency Power Off can be connected to the UPS system.
Pressing the general shutdown button causes UPS shutdown and opening of the battery circuit breaker
(with opening of the bypass static switch depending on customisation settings). The Remote Emergency
Power Off (REPO) notion is applicable to installations where pressing the button also causes the upstream
Normal AC source and AC bypass source circuit breakers to open. In parallel systems, there must be a
single general shutdown button with a separate contact for each UPS unit.
Compliance
The MGE Galaxy 5000 conforms with the following regulatory approvals:
cUL Listed
EN/IEC 62040–1
EN/IEC 62040–2
EN/IEC 62040–3
FCC Part 15 Class A
ISO 9001
UL 1778
6
MGE Galaxy 5000 Technical Specifications
990–3803–001