APC MGE Galaxy 5000 SUG580S90UL User Manual

Product codes
SUG580S90UL
Page of 22
Environmental
Operating Temperature
0 - 40 °C (32-104ºF)
Storage Temperature
-20 - 45 °C (-4-113ºF)
Operating Relative Humidity
0 - 95%, non-condensing
Storage Relative Humidity
0 - 95%, non-condensing
Operating Elevation
0-1000 m (0–3000 ft)): 100% load
At 1500 m (4500 ft): 85% load
At 2000 m (6000 ft): 79% load
At 2300 m (7500 ft): 75% load
At 3000 m (10000 ft): 69% load
At 4000 m (13000 ft): 59% load
Storage Elevation
0-12000 meters (0-40000 ft )
Audible noise at 100% load – 1 meter from surface of
unit
40 kVA 480 V
50 kVA 480 V
60 kVA 480 V
80 kVA 480 V
100 kVA 480 V
130 kVA 480 V
63 dBA
63 dBA
63 dBA
63 dBA
65 dBA
65 dBA
Protection Class
IP20
Colour
Charcoal
Heat Dissipation
40 kVA
50 kVA
60 kVA
80 kVA
100 kVA
130 kVA
Typical losses
(kW)
2.63
3.23
3.75
4.92
5.24
6.81
Heat
dissipation
(BTU/hr)
8974
11021
12796
16788
17880
23237
10
MGE Galaxy 5000 Technical Specifications
990–3803–001