Specifications
Input:
• Input 115VAC 60Hz, 3.5 amp.
•  Input fuse rated @ 3.5 amp/250V.
Output:
•  12VDC or 24VDC selectable output.
  Burglar Alarm Applications (UL 603):
  12VDC = 10VDC-13.2VDC.
  24VDC = 20VDC-26.4VDC.
•  2.5 amp total supply current.
•  Filtered and electronically regulated output.
•  Short circuit and thermal overload protection.
Battery Backup:
•  Built-in charger for sealed lead acid or 
  gel type batteries.
•  Automatic switch over to stand-by battery 
  when AC fails.
•  Maximum charge current 0.7 amp.
Supervision:
•  AC fail supervision (form “C” contacts). 
•  Low battery supervision (form “C” contacts). 
•  Battery presence supervision (form “C” contacts).
Visual Indicators:
•  AC input, DC output and Battery LED indicators.
Electrical:
•  Operating temperature: 0º C to 49º C ambient.
•  BTU/Hr. :
  12VDC: 14.71 - 16.63 BTU/Hr.
  24VDC: 29.43 - 32.41 BTU/Hr.
•  System AC input VA requirement: 402.5VA.
Mechanical:
•  Board Dimensions (W x L x H, approx.):
  4.5” (114.3mm x 7.1” (180.34mm)  x 1.44”(36.58mm)
•  Product weight (approx.): 1.4 lbs. (0.64 kg).
•  Shipping weight (approx.): 1.6 lbs. (0.73 kg).
AL300ULXB2  is  a  power  supply/charger  that  converts  a  115VAC  50/60Hz 
input into a Class 2 Rated power limited 12VDC or 24VDC output
AL300ULXB2
Power Supply/Charger
Rev. DSAL300ULXB2_12142012
Overview
AL300ULXB2
Agency Approvals
7.1"
(180.34mm)
4.5"
(114.3mm)
6.7"
(170.18mm)
3.7"
(93.98mm)
0.34"
(8.64mm)
0.182"
(4.62mm)
o0.156"
(3.96mm)
UL Recognized component for Access Control System Units (UL 294),
Standard for Power Supplies for Use with Burglar-Alarm Systems (UL 603),
Hospital Signaling and Nurse Call Equipment (UL 1069),
Standard for Safety for Fire Protective Signaling Systems (UL 1481).
Board Dimensions 
(L x W x H) (approximate)
:
4.5” (114.3mm) x 7.1” (180.34mm) x 1.44” (36.57mm)