LANDE LN-LCD1708 User Manual

Page of 8
Automatic
Alarm
User defined
Alarm
System automatic
Alarm
Input/output
Product Part Number
LN-PRZ-IZP-DM20-IE
Main Function
Monitor
Keep the former state
Energy consumption metering
Alarm
Daisy-chain
Log record
Time management
User management
Accessing method
Software system
Input
Output
Dimension
Sensor
Optional Accessories
Parameter
Product Description
20xIEC 320 (16xC13 + 4xC19) Socket,  MONITORED IP PDU with Ampermeter Display,
ZeroU, aluminium profile frame, 1x32A MCB, 8000 Watt, 250V AC, 3x6.0mm2, 3m cord
with IEC60309 plug (32A 2P+E), CE mark, daisy-chain function upto 10 units, Remote
Monitoring port
Total load current 
Input voltage 
Total energy consumption (kWh)
Total power (kW) and power factor 
System operating state (RUN indicator) 
Temperature and humidity state 
Keep the former state of group or individual outlet after reset 
Threshold of total load current 
Threshold of temperature and humidity
 Threshold of total load current is exceeded 
Record the total energy consumption (kWh)  
RUN indicator on controlling panel flashes and buzzer sounds 
Indicator on Web interface flashes 
Send Email to administrator automatically 
Send SMS to administrator (not available in some countries) 
SNMP send Trap alarm information 
Logical port output level signal (RJ11 port, ≤50VDC)
10 NPM for daisy-chain (≤5 is suggested) 
Record and save the operation and alarm information which can be checked and output 
SNTP to realize network time synchronization 
Different user permission configuration 
Outlet alarm permission configuration 
Set the permission to clear the energy consumption (kWh)number 
Web, access via IE 
SNMP V1,V2 support 
Telnet, SSH (optional) 
Multi-user operation system, support software upgrade 
Rated input voltage
Input terminal type
Cable specification
Cable length
Plug Type
The max input current
Outlet standard
Outlet standard
Rated output voltage
Product size
250V~50/60 Hz
IEC 60309 plug
3×6.0mm²;
3 M
IEC60309 plug (32A 2P+E)
32A
IEC320 C13 socket Rated current 10A 16 way
IEC320 C19 socket Rated current 16A 4 way
250VAC
WXDXH =44x66x1354mm
Water-logging, Door Open, Smoke, Temperature/humidity 
Vertical Monitored PDU
www.lande.com.tr
COMPLIMENTARY RANGE of 
 
A C C E S S O R I E S
P r o f e s s i o n a l   P D U
3