Lappkabel 0021811, ÖLFLEX® ROBUST 200 Control Data Cable, 3 x 2.5 mm², Black Sheath 0021811 Data Sheet

Product codes
0021811
Page of 1
U.I. Lapp 
GmbH 
DATA SHEET 
 
 
 
 
 
ÖLFLEX
®
  ROBUST 200
 
 
valid from: 03.11.2009
 
 
 
Originator: H. Schillinger / PDC
 
approved: H. Pfeffer/ PDC 
Document: 
DB0021800EN 
page 1 of 1 
All deviations from this specification are subject to explicit consent of U.I. Lapp GmbH. All rights reserved acc. to DIN 34.  
PD 0019/02_10.09EN 
 
Application 
 
ÖLFLEX
 ROBUST 200 cables are connecting cables for flexible use and fixed installation for a robust mechanical use. They 
are for  use  in dry,  damp  and  wet rooms. Under following to the indicate temperature range is  an use outside  possible. At 
room temperature they are increased resistant against acids, caustics solutions and certain oils, greases, waxes of vegeta-
ble, animal, mineral and/or synthetic basis. ÖLFLEX
 ROBUST 200 cables are used as flexible connecting cable in machine 
tool manufacture, plant engineering, in power stations, in heating and air conditioning installations, agriculture, food-, phar-
maceutical- and cosmetically industry, in composting- and sewage plants, by the production of textile fiber, of water based 
purification  plants  by  industrial  and  private  use.  Suitable  for  freely  moved,  not  permanently  recurrent  movement  without 
forced guidance and tensile stress.  
 
 
Technical data 
 
Design 
based on HD 22.10 S2 resp. VDE 0282-10  
 
Conductor 
bare copper, fine wire strand in accordance to IEC 60228 resp. VDE 0295, class 5 
 
Core insulation 
Special PP based compound  
 
Identification 
up to 5 cores coloured acc. to HD308 S2 resp. VDE 0293-308  
                                             more than 6 cores: Black cores with white numbers  
 
with or without GN/YE ground conductor acc. to DIN EN 50334 resp. VDE 0293-334 
 
Outer sheath 
TPE compound, black 
 
Nominal voltage 
450 / 750 V 
 
Test voltage 
4000 V AC 
 
Min. bending radius  
occasional flexing:      10 x cable diameter 
 
fixed installation:          4 x cable diameter 
 
Temp. range 
occasional flexing :      -40 up to +80° C max. conductor temperature 
 
fixed installation           -50 up to +80° C max. conductor temperature 
 
Tests 
acc. to IEC 60811 resp. VDE 0473 and VDE 0472 
 
EC directive 
This cable is conform to ECD 2006/95/EC (Low Voltage Directive).