c. When you have finished creating your Advanced Threshold, click OK to save the schedule and 
return to the Thresholds task.
– Select an Alert Severity value for this threshold. Available Alert Severities are, in order of 
escalating severity: Information, Warning, Error, Critical, or Failure. By default, the Alert 
Severity generated by this threshold will be “Error.”
– Select Cameras to Trigger in response to the alert. To include images from one or more connected 
NetBotz Camera Pod 120s, check the check boxes that correspond to the desired pods. 
– Specify a User-specified URL and User-specified Description. You can use these fields to include 
additional user-specific information with any alert notifications that are generated using this 
threshold. 
– Check the Return-To-Normal Requires User Input check box. When checked, if this threshold is 
exceeded the sensor will not report a Return-To-Normal state until a user with Administrator or 
Application (with Alert Update) privileges opens the resulting alert entry in the Alerts View and 
clicks the Mark Alert Resolved button.
7. Click OK to save this threshold.
Below Value for Time Threshold
A below value for time threshold is defined by specifying a minimum acceptable value for selected 
sensors and a maximum period of time value. If the value reported by the sensor falls below the specified 
value for more than the specified period of time an alert condition is reported. 
To define a below value for time threshold:
1. Launch the Sensor & Alert Settings task that corresponds to the numeric-based sensor for which 
you will define a threshold.
2. Select Below Value for Time Threshold from the Threshold drop box. Any selected devices that 
have previously defined below value for time thresholds will be listed in the Management Devices