Using Post Only Mode with InfraStruXure Central
InfraStruXure Central 4.1 User’s Reference
265
When you have finished providing the needed data, click OK to continue.
6. The InfraStruXure Central server data you entered should now appear in the InfraStruXure Central 
server selection list. If desired, test the Post Only configuration by selecting the new InfraStruXure 
Central server entry from the selection list and then clicking Post to InfraStruXure Central Now. 
After a brief delay, the Status field beside the selected entry should update to indicate that the post 
was successful.
A Note About Posting Interval Considerations
When specifying a posting interval, be sure to consider the size of the alerts that include pictures relative 
to how much memory is available on the device. In general, devices are configured to send a subset of 
their picture data to InfraStruXure Central at the time of the alert and then have InfraStruXure Central 
retrieve the rest of the pictures later. In Post Only mode, the next opportunity for InfraStruXure Central to 
retrieve the remaining pictures will be at the next post interval. However, depending on device model, the 
number of pictures that are currently stored on the device, and the occurrence of subsequent alerts, there 
is a possibility the pictures could be gone by the time the next post occurs. 
SSL Options
Select from this drop box the selection that corresponds to the 
SSL communication options that you want to apply to 
communications between the device and the InfraStruXure 
Central server. You can choose the following options:
• Do not user SSL: Do not use SSL for data delivery, even if 
supported 
• Require SSL: No verification: Require SSL support on the 
server (do not deliver without it), but accept any certificate 
provided by the server (i.e. self signed certificates will be 
allowed). 
• Require SSL - verify certificate: Require SSL support on the 
server (do not deliver without it), and only accept certificates 
signed by a trusted certificate authority (i.e. self signed 
certificates will not be allowed, but Verisign and the like 
certificates will be accepted even if the hostname does not 
match the host in the certificate).
• Require SSL - verify certificate and hostname: Require SSL 
support on the server (do not deliver without it), and only 
accept certificates signed by a trusted certificate authority and 
which contain a hostname matching that used to contact the 
server (i.e. only certificates issued by trusted sources and 
which contain the same hostname as used to access the server 
are allowed). 
Interval Between Posts
Use the controls to specify the number of minutes that will be 
allowed to pass between automatic sensor data posts to the 
InfraStruXure Central server. Note that if an alert is reported, the 
device will post the alert data immediately.
InfraStruXure Central User ID
The user ID of a user account on the InfraStruXure Central 
server that has Administrator access. 
InfraStruXure Central Password
The password that corresponds to the InfraStruXure Central 
User ID account.
Field
Description