UMG 96RM-M
Mean value
Mean values are formed over an adjustable period
for the current, voltage and power measured values.
The mean values are identified with a bar above
the measured value.
The averaging time can be selected from a list of nine
fixed averaging times.
for the current, voltage and power measured values.
The mean values are identified with a bar above
the measured value.
The averaging time can be selected from a list of nine
fixed averaging times.
Current averaging time (addr. 040)
Power averaging time (addr. 041)
Voltage averaging time (addr. 042)
Power averaging time (addr. 041)
Voltage averaging time (addr. 042)
Setting
Baud rate
0
300 Baud
1
600 Baud
2
1200 Baud
3
2400 Baud
4
4800 Baud
5
9600 Baud
6
19200 Baud
7
38400 Baud
Baud rate (addr. 001)
A common baud rate is adjustable for the M-Bus inter-
faces. The baud rate must be chosen to be a uniform
value in the network. The parameter data bits (8), parity
(even) and stop bits (1) are permanently set.
faces. The baud rate must be chosen to be a uniform
value in the network. The parameter data bits (8), parity
(even) and stop bits (1) are permanently set.
Setting
Averaging time/sec.
0
5
1
10
2
15
3
30
4
60
5
300
6
480 (factory setting)
7
600
8
900