DEFAULT CONFIGURATION (Standard-Konfiguration)
HAUPTMENÜ
PARAMETER
EINSTELLUNGEN
System
Vierleiter
Freq[Hz]
50
Clamp Type
FLEX
FS Clamp[A]
3000
Analysator-
Einstellungen
Einstellungen
VT Ratio
1
Zoom Graphics
AUTO
Harm. Type
ALL
Harm. Values
ABSOLUTES
Zoom 1st Harm.
YES
Analysator-
Einstellungen –
Erweitert
Einstellungen –
Erweitert
Average Values
NO
Comments
DEFAULT
Start
Manu
Stop
Manu
Integration period
15min
Cogeneration
OFF
V1N,V2N,V3N,VN-PE,V12,V23,V31,
I1, I2, I3, IN (nur PQA82x), Hz
General Parameter
Pt, P1,P2,P3, Qti, Qi1, Qi2, Qi3, Qtc, Qc1,
Qc2, Qc3, St, S1, S2, S3, Pft, Pft1, Pft2, Pft3,
Cosphit, Cosphi1, Cosphi2, Cosphi3, Eat, Ea1,
Ea2, Ea3, Erit, Eri1, Eri2, Eri3, Erct, Erc1,
Erc2, Erc3
Voltage harmonics
THD, DC, h1, h2, h3[h11
Current harmonics
THD, DC, h1, h2, h3[h11
Voltage anomalies
ON
Ref. Voltage anomalies
230V
Up threshold anomalies
+6%
Down threshold anomalies
-10%
Inrush current (nur PQA82x)
OFF
Flicker
OFF
Unbalance
ON
Messeinstellungen
Spikes (nur PQA824)
ON (150V)
Tafel 14: Parameter bei default configuration ( Grundeinstellung)
ACHTUNG
Die DEFAULT-Konfiguration definiert die vom Hersteller für das Messgerät
gewählten Parameter, wie in Tafel 12 dargestellt. Jede vom Benutzer im
Untermenü „Analyzer Settings” durchgeführte und gespeicherte Modifi-
kation ersetzt diese Konfiguration durch eine neue Auswahl, die sich von
der Standard-Konfiguration unterscheiden kann.
gewählten Parameter, wie in Tafel 12 dargestellt. Jede vom Benutzer im
Untermenü „Analyzer Settings” durchgeführte und gespeicherte Modifi-
kation ersetzt diese Konfiguration durch eine neue Auswahl, die sich von
der Standard-Konfiguration unterscheiden kann.