Module and Card Replacement
Symmetra PX 10-40 kW 208 V Operation & Maintenance Guide - 990-4104
C
23
How to replace Intelligence Modules

Loosen the 2 Phillips screws on both sides of the module (top of module). As soon as the left 
side screw is loose, the module will be deactivated. Display shows message saying the number 
of Cards has been decreased. 

Reverse procedures for installation of replacement module.
How to obtain replacement Modules
To obtain a replacement module, contact APC Customer Support.
1. In the event of a module failure, the display interface may display additional “fault list” screens. 
Press any key to scroll through these fault lists, record the information, and relay it to the 
customer support representative.
2. If possible, call APC Customer Support from a telephone that is within reach of the UPS display 
interface so that you can gather and report additional information to the representative.
3. Be prepared to provide a detailed description of the problem. A representative will help you 
solve the problem over the telephone, if possible, or will give you a return material 
authorization (RMA) number. If a module is returned to APC, this RMA number must be 
clearly printed on the outside of the package.
4. If the Symmetra PX UPS is within the warranty period, repairs will be performed free of charge. 
If it is not within the warranty period, there will be a charge for repair. Review APC ‘s warranty 
policy.
5. If the UPS is covered by an APC service contract, have that information available and provide it 
to the representative.
One Intelligence Module can be replaced without interrupting power to the connected equipment, 
provided a second Intelligence Module is installed and operational.
INTELLI
GENCE
 MODULE
INTELLIGENCE MO
DULE
INTELLIGENCE MODULE
INTELLIGENCE MODULE

See section on
 
Warranty for more information