APC Smart-UPS On-Line, 1050 Watts / 1500 VA,Input 120V / Output 120V, Interface Port DB-9 RS-232, Smart-Slot, USB, Rack Height 2 U SURTA1500RMXL User Manual
![APC](https://files.manualsbrain.com/attachments/434134065d5c651f4d733496e262a45a75ce3ca6/common/fit/150/50/cb1a8b6f231ef4d783dd99279a1457344a0d4d6facb230ab9b5ba2f65edf/brand_logo.png)
Product codes
SURTA1500RMXL
Operation
6
Smart-UPS RT SURTA1500XL/SURTA1500XLJ/SURTA2000XL Uninterruptible Power Supply User Manual
b. Select the COM port that is connected to the UPS. The port settings are:
• Bits per second - 2400
• data - bits 8
• parity - none
• stop bit - 1
• flow control - none
• data - bits 8
• parity - none
• stop bit - 1
• flow control - none
c. Press Enter.
4. Once the terminal window is open, follow these steps to set the number of external battery packs
(SURTA48XLBP or SURTA48XLBPJ):
a. Press Enter to initiate terminal mode. Follow the prompts.
b. Press 1 to modify UPS settings. Press e (or E) to modify the number of battery packs.
c. Enter the number of battery packs, including the internal battery module (Number of packs: 1 =
a. Press Enter to initiate terminal mode. Follow the prompts.
b. Press 1 to modify UPS settings. Press e (or E) to modify the number of battery packs.
c. Enter the number of battery packs, including the internal battery module (Number of packs: 1 =
internal battery module, 2 = one SURTA48XLBP or SURTA48XLBPJ, 3 = two
SURTA48XLBP or SURTA48XLBPJ, etc.)
SURTA48XLBP or SURTA48XLBPJ, etc.)
d. Press Enter.
e. Follow the prompts.
e. Follow the prompts.
5. Exit the terminal program.
Operation
Display Panel
Display Panel Indicators
Indicator
LED
Indicator Title
Description
On Line
The UPS is supplying utility power to the connected equipment.
On Battery
The UPS is supplying battery power to the connected equipment.
85%
68%
51%
34%
17%
68%
51%
34%
17%
96%
72%
48%
24%
0%
72%
48%
24%
0%
Load
Percentages
Battery Charge
Percentages