Tele OVP1 24 V/AC/DC 0 - 10 V 170012 170012 Data Sheet

Product codes
170012
Page of 2
Subject to alterations and errors
Release 11/02
Coupling relays - OCTO series
Installation design
Width 17.5mm
Analog data encoder 0 to 10VDC
Checkback signal of the switch setting ‚AUTO‘
Technical data
1. Functions
AUTO 
output according to input YR
permanently OFF
HAND 
output according to set value (regulator)
2. Indicators
Yellow LED ON/OFF: 
intensity according to the value of the
 
 
output signal
3. Mechanical design
Self-extinguishing plastic housing, IP rating IP40
Mounted on DIN-Rail TS 35 according to EN 50022
Mounting position: 
any
Shockproof terminal connection according to VBG 4
(PZ1 required), IP rating IP20
Initial torque: 
max. 1Nm
Terminal capacity:
 
1 x 0.5 to 2.5mm² with/without multicore cable end
 
1 x 4mm² without multicore cable end
 
2 x 0.5 to 1.5mm² with/without multicore cable end
 
2 x 2.5mm² flexible without multicore cable end
4. Input circuit
Supply voltage: 
24V AC/DC 
terminals A1(+)-A2
Tolerance: 
24V AC/DC 
-15% to +10%
Rated frequency: 
48 to 63Hz
Rated consumption: 
24V AC/DC 
0.58VA (0.33W)
Duration of operation: 
100%
Reset time: 
-
Residual ripple for DC: 
10%
Drop-out voltage: 
>30% of supply voltage
5. Output circuit
Output signal (terminals Y-GND):
 
Switch setting AUTO 
corresponding to input signal at
 
 
terminals YR - GND
 
Switch setting 0 
0V 
 
Switch setting HAND 
0 to 10V 
Output capacity Y: 
10mW at 10V 
 
 
(switch setting HAND)
Insulation voltage: 
24V AC (according to IEC 664-1)
Surge voltage: 
800V, overvoltage category III
 
 
(according to IEC 664-1)
6. Checkback
Setting ‚AUTO‘: 
terminals B1-B2
Maximum switching capacity: 56VA (2A / 28V AC/DC)
Minimum switching capacity:  5mVA (1mA / 5V AC/DC)
Contact resistance:  
max. 20mΩ
Electrical life: 
3 x 10
4
 operations at maximum load
7. Accuracy
Base accuracy: 
±1% (of maximum scale value)
Adjustment accuracy: 
±10% (of maximum scale value)
Repetition accuracy: 
-
Voltage inuence: 
-
Temperature inuence: 
≤0.01% / °C
8. Ambient conditions
Ambient temperature: 
-25 to +55°C (according to IEC 68-1)
Storage temperature: 
-25 to +70°C
Transport temperature: 
-25 to +70°C
Relative humidity: 
15% to 85%
 
(according to IEC 721-3-3 class 3K3)
Pollution degree: 
2, if built-in 3
 
(according to IEC 664-1)
OVP1