Tele 170010 Relay 1 changeover contact 170010 Data Sheet

Product codes
170010
Page of 2
Coupling relays - OCTO series
HAR1
Installation design
Width 17.5mm
Three-way switch:
permanently OFF or ON, automatic
Checkback signal of the switch setting 'AUTO‘
1 change over contact
4.02 – 1
7. Ambient conditions
Ambient temperature:          -25 to +55°C (according to IEC 68-1)
Storage temperature:            -25 to +70°C
Transport temperature:         -25 to +70°C
Relative humidity:                  15% to 85%
                                                (according to IEC 721-3-3 class 3K3)
Pollution degree:                   2, if built-in 3
                                                (according to IEC 664-1)
8. Dimensions
1. Functions
AUTO 
automatic
permanently OFF
HAND 
permanently ON
2. Indicators
Yellow LED ON/OFF: 
indication of relay output
3. Mechanical design
Self-extinguishing plastic housing, IP rating IP40
Mounted on DIN-Rail TS 35 according to EN 50022
Mounting position: 
any
Shockproof terminal connection according to VBG 4
(PZ1 required), IP rating IP20
Initial torque: 
max. 1Nm
Terminal capacity:
              1 x 0.5 to 2.5mm² with/without multicore cable end
              1 x 4mm² without multicore cable end
              2 x 0.5 to 1.5mm² with/without multicore cable end
              2 x 2.5mm² flexible without multicore cable end
4. Input circuit
Supply voltage: 
24V AC/DC 
terminals A1(+)-A2
Signal voltage: 
24V AC/DC 
terminals A3(+)-A2
Tolerance: 
-15% to +10%
Rated frequency: 
48 to 63Hz
Rated consumption: 
0.5VA (0.5W)
Duration of operation:  100%
Reset time: 
-
Residual ripple for DC:  10%
Drop-out voltage: 
>10% of supply voltage
5. Output circuit
1 potential free change over contact
Switching capacity (distance < 5mm): 
1250VA (5A / 250V AC)
Switching capacity (distance > 5mm): 
2000VA (8A / 250V AC)
Fusing: 
8A fast acting
Mechanical life: 
20 x 10
6
 operations
Electrical life: 
2 x 10
5
 operations
 
at 1000VA resistive load
Switching frequency:  max. 60/min at 100VA resistive load
 
max. 6/min at 1000VA resistive load
 
(according to IEC 947-5-1)
Insulation voltage: 
250V AC (according to IEC 664-1)
Surge voltage: 
4kV, overvoltage category III
 
(according to IEC 664-1)
6. Check-back
Position 'AUTO‘: 
terminals B1-B2
Maximal switching capacity: 
24VA (500mA / 48V AC/DC)
Minimal switching capacity: 
5mVA (1mA / 5V AC/DC)
Contact resistance: 
max. 20mΩ
Electrical life: 
3 x 10
4
 operations
 
at maximum load
Technical data
Subject to alterations and errors
Release 11/01