Yuasa YPC55-12, 12V Ah lead acid battery YPC55/12 YPC55/12 Data Sheet
Product codes
YPC55/12
YPC55-12
Nominal voltage
12
V
20-hr rate Capacity to 10.5V at 20°C
53.4
Ah
10-hr rate Capacity to 10.8V at 20°C
50.0
Ah
Length
229 (±2)
mm
Width
138 (±2)
mm
Height
205 (±2)
mm
(height over terminals)
211 (±2)
mm
Mass (typical)
17.0
kg
Female threaded terminal
M6
mm
Torque
5.4
Nm
Storage (in fully charged condition)
Charge
Discharge
LAYOUT
Capacity loss per month at 20°C (approx)
3
%
Standard Option
Flame retardant option (FR)
13.65 (±1%)
V
2.275 (±1%)
V/cell
Float Charge voltage temperature correction factor
(for variations from the standard 20°C)
(for variations from the standard 20°C)
-3
mV/cell/°C
14.5 (±3%)
V
2.42 (±3%)
V/cell
Cyclic Charge voltage temperature correction factor
(for variations from the standard 20°C)
(for variations from the standard 20°C)
-4
mV/cell/°C
Float charge current limit
No limit
A
Cyclic (or Boost) charge current limit
13.35
A
1 second
660
A
1 minute
534
A
3RD PARTY CERTIFICATIONS
ISO 9001 - Quality Management Systems
100% DOD down to 80% capacity
300
cycles
ISO 14001 - Environmental Management Systems
75% DOD down to 80% capacity
500
cycles
EN 18001 - OHSAS Management Systems
50% DOD down to 80% capacity
600
cycles
25% DOD down to 80% capacity
1400
cycles
UNDERWRITERS LABORATORIES Inc.
Measured at 1 kHz
7.5
m
Ω
STANDARDS
Refer to the technical short form
YPC
IEC61056
IEC60895-21/22
EUROBAT Classification: Standard Commercial
3 to 5
years
ALL DATA IS SUBJECT TO CHANGE WITHOUT NOTICE
Issue No.: V.5 / Issue Date: Mar 2012
YPC-Series - Valve Regulated Lead Acid Battery
SPECIFICATIONS
DIMENSIONS
TERMINAL TYPE
OPERATING TEMPERATURE RANGE
-20°C to +60°C
-15°C to +50°C
-20°C to +60°C
STORAGE
CASE MATERIAL
ABS (UL.94:HB)
ABS (UL94:V0)
CHARGE VOLTAGE
Float charge voltage at 20°C
Cyclic (or Boost) charge at 20°C
CHARGE CURRENT
MAXIMUM DISCHARGE CURRENT
CYCLIC LIFE DATA
IMPEDANCE
PERFORMANCE & CHARACTERISTICS
DESIGN LIFE
SAFETY
Installation
Installation
Can be installed and operated in any orientation except permanently inverted
YUASA BATTERY SALES UK LTD.
Unit 13, Hunts Rise
South Marston Industrial Estate
Swindon
SN3 4TG
UK
Unit 13, Hunts Rise
South Marston Industrial Estate
Swindon
SN3 4TG
UK
Recycling
YUASA's VRLA batteries must be recycled at the end of life in accordance with local and national
laws and regulations
laws and regulations
Handles
Batteries must not be left permanently suspended by their handles (where fitted)
Vent valves
Vent valves
Each cell is fitted with a low pressure release valve to allow gasses to escape and then reseal.
Gas Release
Gas Release
VRLA Batteries release hydrogen gas which can form explosive mixtures in air. Do not place inside
a sealed container
a sealed container