Vision Akkus VISION 6FM55DX, 12V Ah lead acid battery 6FM55DX 6FM55DX Data Sheet

Product codes
6FM55DX
Page of 2
6FM55D-X
12V 55Ah(10hr) 
The rechargeable batteries are lead-lead dioxide systems. The dilute sulfuric acid electrolyte 
is absorbed by separators and plates and thus immobilized. Should the battery be 
accidentally overcharged producing hydrogen and oxygen, special one-way valves allow the 
gases to escape thus avoiding excessive pressure build-up. Otherwise, the battery is 
completely sealed and is, therefore, maintenance-free, leak proof and usable in any position. 
Battery Construction
Component
Positive plate
Negative plate
Container
Cover
Safety valve
Terminal
Separator
Electrolyte
Raw material
Lead dioxide
Lead
ABS
ABS
Rubber
Pb
Fiberglass
Sulfuric acid
General Features 
Absorbent Glass Mat (AGM) technology 
for efficient gas recombination of up to 
99% and freedom from electrolyte 
maintenance or water adding.
Not restricted for air transport-complies 
with IATA/ICAO Special Provision A67.
UL-recognized component.
Can be mounted in any orientation.
Computer designed lead, calcium tin alloy 
grid for high power density.
Long service life, float or cyclic 
applications.
Maintenance-free operation.
Low self discharge.
Dimensions and Weight
Length(mm / inch)
239 / 9.41
Width(mm / inch)
132 / 5.20
Height(mm / inch) 
205 / 8.07
Total Height(mm / inch) 
210 / 8.27
Approx. Weight(Kg / lbs) 
18 / 39.7 
Performance Characteristics 
Nominal Voltage
12V
Number of cell
6
Design Life 
10 years 
Nominal Capacity 77
o
F(25
o
C)
10 hour rate (5.50A, 10.8V)
55.0Ah
5 hour rate (9.05A, 10.5V)
45.25Ah
1 hour rate (34A, 9.6V)
34Ah
Internal Resistance
Fully Charged battery 77
o
F(25
o
C)
5.8mOhms
Self-Discharge
3% of capacity declined per month at 20
o
C(average)
Operating Temperature Range
Discharge
-20~60
o
C
Charge
-10~60
o
C
Storage
-20~60
o
C
Max. Discharge Current 77
o
F(25
o
C)
550A(5s)
Short Circuit Current
1400A
Charge Methods: Constant Voltage Charge 77
o
F(25
o
C)
Cycle use
14.4-14.7V
        Maximum charging current
16.5A
        Temperature compensation 
-30mV/
o
C
Standby use 
13.6-13.8V
        Temperature compensation 
-20mV/
o
C
Discharge Constant Current (Amperes at 77
o
F25
o
C)
Discharge Constant Power (Watts at 77
o
F25
o
C)
page1 of 2
www.vision-batt.com
(Note)The above characteristics data are average values obtained within 
three charge/discharge cycles not the mimimum values.
End Point
Volts/cell
5min 10min 15min 30min
1h
3h
5h
10h
20h
100h
1.60V
181
133
103
61.1
36.2
15.2
10.2
5.69
2.94
0.66
1.65V
170
128
98.4
59.3
35.3
14.8
9.98
5.66
2.94
0.66
1.70V
160
119
93.5
57.3
34.4
14.5
9.80
5.61
2.94
0.66
1.75V
150
110
88.5
55.5
33.5
14.1
9.63
5.55
2.93
0.66
1.80V
138
103
82.0
53.5
32.7
13.8
9.45
5.50
2.93
0.66
End Point
Volts/cell
5min 10min 15min 30min 45min
1h
2h
3h
5h
100h
1.60V
328
246
190
115
88.0 71.1 42.7 30.3 19.6 1.33
1.65V
310
232
183
113
86.7 69.5 41.7 29.7 19.4 1.33
1.70V
290
220
174
111
84.9 67.9 40.9 29.0 18.9 1.33
1.75V
269
206
167
109
83.1 66.4 39.8 28.5 18.7 1.33
1.80V
256
191
159
107
80.9 66.4 38.8 27.9 18.6 1.33