Wachendorff ZD327401 Data Sheet

Page of 2
MEMORY CARD (optional)
MEMORY CARD (optional)
Parameters and setpoint values can be copied from one device to
another using the Memory card
There are two methods:
insert the memory card when the controller is off.
On activation display 1 shows and display 2 shows
The device loads the new data and starts again
The memory card is equipped with an internal battery with a life of about 1000 uses.
Insert the memory card and press the programming button.
When writing the parameters, the LED turns red and on completing the procedure it
changes to green. It is possible to repeat the procedure.
To
the memory card values, follow the procedure described in the first
method, setting display 2 to
so as not to load the parameters on controller.
Enter configuration and change at least one parameter.
Exit configuration. Changes are saved automatically.
This procedure restores the factory settings of the instrument.
With the device connected to the power supply
With the controller disconnected from the power supply:
update
LOADING DEFAULT VALUES
. Attention: Pls. perform first an update of the
memory card.
(Only if the values stored on Memory Card are correct).
By pressing the
key display 2 shows
Confirm using the
key .
.
>
>
UPDATING MEMORY CARD.
SIZE AND INSTALLATION
SIZE AND INSTALLATION
INTRODUCTION
The ZD327401 can
be set in 2 different modes: Single or Double counter, all with independent
settings. 3 universal digital inputs are available (NPN/PNP
) and can be used for bidirectional encoders reading, UP/DOWN counter
function, LOCK/HOLD to lock or hold current visualization.One input is also
analogue in order to allow setpoint modification by an external potentiometer.
Thanks for choosing a Wachendorff Prozesstechnik device.
/Potential free
contact
WIRING DIAGRAM
WIRING DIAGRAM
Potentiometer:
1
2
3-
4
Hin.3
Fin.3
Set1
Set2 P.tAr
To modify Set1 or Set2 by external potentiometer follow the steps below:
-use potentiometers 0 to 5/10kohm
-connect cursor to pin I3; a wrong connection may damage the potentiometer and
lead to lock of the device.
accuracy on input is max 1000 points, therefore set the parameters "Upper limit"
and "Lower limit" with a max difference of 1000 units.
(Ex.: LoS1 to 50,0 and uPS1 to 150,0 to modify preset
value related to Set1
between 50 and 150 pulsess with steps of one tenth). Greater differences would
make unstable the less significant digit.
-To calibrate the scale of potentiometer enter the configuration mode and select:
as Pot
as
or
as Enable
Exit configuration mode and place potentiometer at minimum level and press
key,
then place potentiometer at max level and press premere
key: the device
automatically exit the calibration procedure.
N.B.: A switch-off of the device would interrupt the calibration.
PRESS
for 3 seconds
Display 1 shows
and 1st digit flashes.
Display 2 shows
DISPLAY
DO
or
Modify flashing digit and
pass to the next one pressing
Enter password
to confirm
Display shows first parameter
of configuration table
1
2
3
Scroll parameters
4
or
Increase or decrease visualized value
by pressing
and an arrow key.
Enter the new data
which will be stored
releasing the keys
5
+
or
End configuration, controller
exits from programming mode.
6
MODIFY CONFIGURATION PARAMETERS
MODIFY CONFIGURATION PARAMETERS
Visualizes SETPOINT 1 / 2
or
Modify selected SET
Selects chosen digit
1
2
2a
Modify blinking digit of selected SET
3a
or
PRESS
DISPLAY
SETPOINT MODIFICATION
SETPOINT MODIFICATION
PARAMETERS LIST
PARAMETERS LIST
POTENZIOMETRO 5..10 Kohm
Risoluzione 1000 punti
GND
POSITIVO
Fase
Z
Encoder
Fase
B
Fase
A
PNP
NPN
PNP
NPN
PRESS
for 3 seconds
Display 1 shows
and 1st digit flashes.
Display 2 shows
DISPLAY
DO
or
Modify flashing digit and
pass to the next one pressing
Enter password
to confirm
Device loads
default settings
Switch-off and restart
the device
1
2
3
LOADING DEFAULT VALUE
LOADING DEFAULT VALUE
Disabled
Default
Disable
Load Counter 1
Load Counter 2
Load Counter 1&2
Loading counter 1
Loading counter 2
Loading counters 1 and 2
P-13 Function Key UP
Function associated to UP (up arrow key)
Disabled
Default
Enabled
P-14 Potentiom. Tarature
Potentiometer calibration procedure
Disable
Enable
P-01 Counter Function
FUNCTION CONFIGURATION
P-02 Power-off Memory
BACKUP MEMORY CONFIGURATION
Counter Functions
1 counter functioning
Power-off memory
No counter stored at power-off
Default
Default
Single (1 Counter)
Double (2 Counters)
Counter 1 stored at power-off
Counter 2 stored at power-off
All counters stored at power-off
2 counters functioning
P-03 Hardware input 1
INPUT CONFIGURATION
Input 1 Hardware configuration
NPN (not available on Input 3)
Default
NPN
PNP
TTL
Potent.
PNP
TTL
Potentiometer (available only for Input 3)
P-04 Hardware input 2
Input 2 Hardware configuration
P-05 Hardware input 3
Input 3 Hardware configuration
P-06 Filter Delay Input 1
Input 1 digital filter configuration
Input filter desabled
Default
Filter of 0,5 ms
...(Step 0,5 ms)
P-07 Filter Delay Input 2
Input 2 digital filter configuration
P-08 Filter Delay Input 3
Input 3 digital filter configuration
Disabled
Default
Disable
Encoder Z
Load Counter 1
Load Counter 2
Load Counter 1&2
Set1
Set2
Loading encoder Z
Loading counter 1
Loading counter 2
P-12 Function Input 3
Function associated to Input 3
Loading counters 1 and 2
Set1 setting by potentiometer
Set2 setting by potentiometer
Filter of 100,0 ms
P-09 Active State Input 1
Active state Input 1
P-10 Active State Input 2
Active state Input 2
High level (available only for Input 2)
Default
High Level
Low Level
Rising edge
Falling edge
Low level (available only for Input 2)
Rising edge
Falling edge
COUNTER CLOCK CONFIGURATION
Disabled
Default C2
Disable
Encoder
I1 Up, I2 Off
I1 Down, I2 Off
Bidirectional encoder (I1) phase A, (I2) phase B
UP mode (I1)
DOWN mode (I1)
P-15 Clock Counter 1
Counter 1 count mode selection
P-33 Clock Counter 2
Counter 2 count mode selection
Default C1
UP mode (I2)
DOWN mode (I2)
UP mode (I1) - DOWN mode (I2)
UP mode (I1) with reverse direction (I2)
UP mode (I1) with count lock (I2)
UP mode (I1) with keeping value on display (I2)
DOWN mode (I1) with count lock (I2)
DOWN mode (I1) with keeping value on display (I2)
UP count on rising edge of counter 2/1 output
COUNTER DISPLAY CONFIGURATION
Counter value not visualized
Default C2
Counter value visualized
P-16 Display Counter 1
Counter 1 visualization selection
P-34 Display Counter 2
Counter 2 visualization selection
Default C1
Disable
Visualized
No decimal digit visualization
Default
1 decimal digit visualization
2 decimal digits visualization
3 decimal digits visualization
Default
P-17 Decimal Point Counter 1
Counter 1 visualization format
P-35 Decimal Point Counter 2
Counter 2 visualization format
P-18 Counter 1 input counts
Counter 1 input counts (1...9999)
P-36 Counter 2 input counts
Counter 2 input counts (1...9999)
Default 1
Default 1
P-19 Counter 1 Visualized Counts
Counter 1 visualized counts (1...9999)
P-37 Counter 2 Visualized Counts
Counter 2 visualized counts (1...9999)
Default 1
Default 1
SETPOINT CONFIGURATION
Setpoint value not visualized
Default C2
Setpoint value visualized
P-20 Display Set 1
Counter 1 setpoint visualization selection
P-38 Display Set 2
Counter 2 setpoint visualization selection
Disable
Visualized
Modifiable
Setpoint value visualized and modifiable
Default C1
P-21 Lower Limit Set 1
Set 1 minimum value (0...9999)
P-39 Lower Limit Set 2
Set 2 minimum value (0...9999)
Default 0
Default 0
P-22 Upper Limit Set 1
Set 1 maximum value (0...9999)
P-40 Upper Limit Set 2
Set 2 maximum value (0...9999)
Default 999
Default 999
Automatic loading disabled
Default
Disable
Counter = Set 1
Counter = Set 2
Counter = Set 1+Output Duration 1
Counter = Set 2+Output Duration 2
Counter = Visualized counts
Loading if counter = Set1
Loading if counter = Set2
Loading if counter = Set1 + “Output Duration 1”
P-23 Automatic Load Counter 1
Counter 1 automatic loading
Loading if counter = Set2 + “Output Duration 2”
Loading if counter = “Visualized Counts”
P-41 Automatic Load Counter 2
Counter 2 automatic loading
AUTOMATIC LOAD CONFIGURATION
COUNTER LOAD VALUE CONFIGURATION
P-24 Counter Load Value 1
Counter 1 loading value
P-42 Counter Load Value 2
Counter 2 loading value
Default 0
Default 0
Default
Counter Set
Counter Set * Output Duration (time)
Counter Set * Output Duration (counts)
Counter Set1+Set2
=
=
=
=
Output active if Counter Set
=
Output active for “Output Duration” time if Counter Set
=
Output active for “Output Duration” counts if Counter Set
=
P-25 Counter 1 Output Mode
P-43 Counter 2 Output Mode
Default
Counter 1 output mode
Counter 2 output mode
COUNTER OUTPUT MODE CONFIGURATION
P-46 Decimal Point Frequency Counter 2
P-28 Decimal Point Frequency Counter 1
COUNTER FREQUENCY DISPLAY CONFIGURATION
Counter frequency value not visualized
Default
Counter frequency value visualized
P-27 Display Frequency Counter 1
Counter 1 frequency visualization
P-45 Display Frequency Counter 2
Counter 2 frequency visualization
Disable
Visualized
Default
0
0.0
0.00
0.000
Visualization with 2 decimal digits
Visualization with 3 decimal digits
Visualization with no decimal digit
Default
Visualization with 1 decimal digit
Counter 1 frequency format
Counter 2 frequency format
P-29 Counter 1 Input frequency
Counter 1 input frequency (1...9999Hz)
P-47 Counter 2 Input frequency
Counter 2 input frequency (1...9999Hz)
Default 1
Default 1
P-30 Counter 1 Visualized Frequency
Counter 1 visualized frequency
Default 1
P-48 Counter 2 Visualized Frequency
Counter 2 visualized frequency
Default 1
P-31 Output Q1 Setup
Output Q1 setting
P-32 Output Q2 Setup
Output Q2 setting
Disabled output
Default C1
Counter 1 output on n.o. contact
Counter 1 output on n.c. contact
Counter 2 output on n.o. contact
Counter 2 output on n.c. contact
Default C2
Output active if Counter Set1+Set2
=
Default
Output Duration Input by User
Latch output (clear only by load)
Min output duration
Max output duration
Latch output, resettable by counter loading
Output duration minimum value
Output duration maximum value
P-26 Output 1 Duration
P-44 Output 2 Duration
Value modifiable by user
Default 10
Counter 1 output duration
Counter 2 output duration
OUTPUT DURATION CONFIGURATION
Default 10
Disable
Counter 1
Counter 2
All Counters
I1 Off, I2 Up
I1 Off, I2 Down
I1 Up, I2 Down
I1 Up, I2 Incr./Decr.
I1 Up, I2 En./Lock
I1 Up, I2 En./Hold
I1 Down, I2 En./Lock
I1 Down, I2 En./Hold
Output Counter 2/1
No delay
0,5 ms
...
100,0 ms
0
0.0
0.00
0.000
Disable
Out Counter 1 n.o.
Out Counter 1 n.c.
Out Counter 2 n.o.
Out Counter 2 n.c.
Proximity
Sensor PNP
3 wires
Proximity
Sensor PNP
2 wires
+
-
OUT
OUT
Read carefully the safety guidelines and programming instructions contained in
this manual before using/connecting the device.Disconnect power supply before
proceeding to hardware settings or electrical wirings.Only qualified personnel
should be allowed to use the device and/or service it and in accordance to
technical data and environmental conditions listed in this manual.Do not dispose
electric tools together with household waste materials in observance of
European Directive 2002/96/CE
P-11 Active State Input 3
Active state Input 3
1
2
3
28.5 x 70.5 mm
Frontal panel cut-out
2
mm
Suggested thickness
÷8
77 mm
35
mm
53 mm
7
CN1
1
6
Memory Card (optional)
with battery
Order-no. SFUR0KIT
Gasket for 32x74
TECHNICAL DATA
TECHNICAL DATA
Operating conditions
Sealing
Material
Digital Inputs
Outputs
OUT 24V
Back-UP
Power Supply
Operating temperature 0-40°C, humidity 35..95uR%
PC ABS UL94V0 self-extinguishing
3PNP/NPN configurable as analogue for potentiometers.
2 relays 5A resistive charge
Rechargeable battery, approx. 7days autonomy
24...230Vac/Vdc +/-15% 50/60Hz / 2W
Front panel IP65 (with optional gasket) ,
Box IP30, Terminal blocks IP20
(max 28 Vdc in PNP mode)
30mA(at 24 VAC supply),40 mA(at 24 VDC supply),
60 mA (at 110 to 230 VAC)
Report the activation of Q1
MEANING
Report the activation of Q2
LED
1
2
3
1
2
3
Report serial transmission by the ZD327401
1
2
3
MANUAL
COUNTER ZD327401
MANUAL
COUNTER ZD327401
Wachendorff Prozesstechnik GmbH & Co. KG
www.wp-direkt.de
e-mail: RSS@wachendorff.de
Version 2.0
LOADING DEFAULT VALUES
This procedure restores the factory settings of the instrument.