Benning PROFIPOL Voltage Tester 020022 Data Sheet

Product codes
020022
Page of 20
PROFIPOL
®
Benning Elektrotechnik & Elektronik GmbH & Co. KG
Münsterstraße 135 - 137   •   D - 46397 Bocholt
Phone: +49 (0) 2871 - 93 - 0   •   Fax: +49 (0) 2871 - 93 - 429
www.benning.de   •   E-Mail: duspol@benning.de
T.-Nr
. 755737.1
1/ 03-2010
geprüft und zugelassen
D
 Bedienungsanleitung
 Operating manual
F
 Mode d‘emploi
E
Manuel de instrucciones
  Инструкция за експлоатация
 Návod k použití zkoušečky
Brugsanvisning
 Käyttöohje
 Οδηγίες χρήσεως
H
 Használati utasítás
I
 Istruzioni per l’uso
Naudojimosi instrukcija
N
 Bruksanvisning
 Gebruiksaanwijzing
 Instrukcja obsługi
 Instrucţiuni de utilizare
 Инструкция по эксплуатации 
индикатора напряжения
S
 Bruksanvisning
   Kullanma  Talimati
 Priručnik za upotrebu
Operating manual 
PROFIPOL
®
Before using the voltage tester PROFIPOL
®
: Please 
read  the  operating  manual  carefully  and  always 
observe the safety instructions! 
List of contents:
1.   Safety instructions 
2.   Functional description of the voltage tester
3.   Functional test of the voltage tester 
4.   How to test AC voltages
5.   How to test DC voltages
5.1   How to test the polarity at DC voltage
6.  Technical data
7.  General maintenance
8.   Environmental  notice
1.  Safety instructions:
-   �old  the  �oltage  tester  only  by  the  insulated 
handles   and   and do not touch the contact 
electrodes (probe tips) ! 
-   I��ediately before use: Check the �oltage tester 
for correct operation! (see chapter 3). The �oltage 
tester �ust not be used if one or se�eral display 
functions fail or if the �oltage tester is not ready to 
operate (IEC 61243-3)! 
-   The  �oltage  tester  �ust  be  used  only  within  the 
no�inal �oltage range of 6 V up to 400 V!
-   The �oltage tester co�plies with protection class 
IP 65 and therefore can also be used under wet 
conditions.
-   For testing, fir�ly grasp the �oltage tester by the 
handles   and  . 
-   Ne�er  connect  the  �oltage  tester  to  �oltage  for 
longer  than  30  seconds  (�axi�u�  per�issible 
operating ti�e = 30 s)! 
-   The  �oltage  tester  only  operates  correctly 
within  the  te�perature  range  of  -10 °C  up  to 
+55 °C at relati�e air hu�idity of 20 % up to 96 %. 
-   Do not dis�antle the �oltage tester!
-   Please  protect  the  housing  of  the  �oltage  tester 
against contamination and damages. 
-   Please store the �oltage tester under dry conditions.
Attention:
After  �axi�u�  load  (i.e.  after  a  �easure�ent  of  30 
seconds at 400 V), the �oltage tester �ust not be used 
for a duration of 300 seconds!
2.  Functional description 
The PROFIPOL
®
 is a two-pole �oltage tester according 
to IEC 61243-3 with �isual display  and without own 
power  supply. The  �oltage  tester  is  designed  for  DC 
and AC �oltage tests within the �oltage range of 6 V 
up  to  400 V.  It  can  be  used  to  perfor�  polarity  tests 
in DC. 
The  �oltage  tester  consists  of  the  test  probes  L1   
and L2   and a connecting cable 6. The test probe 
L1   is equipped with a display . 
Display field
The display syste�  consists of high-contrast light-
e�itting  diodes  (LED)  3  indicating  �oltages  in  steps 
of  6 V  to  400 V.  The  indicated  �oltages  are  no�inal 
�oltages. With DC �oltage, the LEDs also indicate the 
polarity (see chapter 5).
3.  Functional check 
-   The  �oltage  tester  �ust  be  used  only  within  the 
no�inal �oltage range of 6 V up to 400 V!
-   Ne�er  connect  the  �oltage  tester  to  �oltage  for 
longer  than  30  seconds  (�axi�u�  per�issible 
operating ti�e = 30 s)!
-   Check  the  �oltage  tester  for  correct  function 
i��ediately before use! 
-   Test  all  functions  by  �eans  of  known  �oltage 
sources. 
 
•    For DC �oltage tests use e.g. a car battery. 
 
•   For AC �oltage tests use e.g. a 230 V socket.
Do not use the �oltage tester unless all functions are 
operating correctly!
4.   How to test AC voltages 
-   The  �oltage  tester  �ust  be  used  only  within  the 
no�inal �oltage range of 6 V up to 400 V!
-   Ne�er  connect  the  �oltage  tester  to  �oltage  for 
longer  than  30  seconds  (�axi�u�  per�issible 
operating ti�e = 30 s)!
-   Place the contact electrodes  of the test probes 
L1   and L2   against the rele�ant points of the 
unit under test. 
-   For AC �oltages fro� 6 V onwards the LEDs “plus” 
and  “�inus”  4 and 5  light  up.  Further�ore, 
all  LEDs  light  until  the  step  �alue  of  the  applied 
voltage is reached.
5.   How to test DC voltages 
-   The  �oltage  tester  �ust  be  used  only  within  the 
no�inal �oltage range of 6 V up to 400 V!
-   Ne�er  connect  the  �oltage  tester  to  �oltage  for 
longer  than  30  seconds  (�axi�u�  per�issible 
operating ti�e = 30 s)!
-   Place the contact electrodes  of the test probes 
L1   and L2   against the rele�ant points of the 
unit under test. 
-   For AC �oltages fro� 6 V onwards the LEDs “plus” 
and  “�inus”  4 and 5  light  up.  Further�ore, 
all  LEDs  light  until  the  step  �alue  of  the  applied 
voltage is reached. 
5.1  How to test the polarity at DC voltage 
-   The  �oltage  tester  �ust  be  used  only  within  the 
no�inal �oltage range of 6 V up to 400 V!
-   Ne�er  connect  the  �oltage  tester  to  �oltage  for 
longer  than  30  seconds  (�axi�u�  per�issible 
operating ti�e = 30 s)!
-   Place the contact electrodes  of the test probes 
L1   and L2   against the rele�ant points of the 
unit under test. 
-   If LED 4 lights up, the “positi�e pole” of the unit 
under test is at test probe  .
-   If LED 5 lights up, the “negati�e pole” of the unit 
under test is at test probe  .  
6.  Technical data
-   �uideline for two-pole �oltage testers: IEC 61243-3 
-  Protection class: IP 65, IEC 60529 (DIN 40050)
 
 IP  65  �eans:  Protection  against  access  to 
dangerous  parts  and  protection  against  solid 
i�purities,  dustproof,  (6  -  first  index).  Protected 
against water jets, (0 - second index).
-   No�inal �oltage range: 6 V to 400 V
-   Internal resistance, �easuring circuit: 130 kΩ
-   Current consu�ption: �ax. I
n
 3.1 �A 
-   Polarity indication: LED +; LED - 
 
(indicating handle = positi�e polarity)
-   Indicating steps LED: 6 V, 12 V, 50 V, 120 V, 230 V, 
400 V
-   �ax. indicating errors: �
n
 ± 15 %, ELV �
n
 - 15 %
-  No�inal frequency range f: 0 to 500 �z
-   �ax. per�issible operating ti�e: 
 
ED = 30 s (�ax. 30 seconds), 300 s pause
-  Weight: approx. 136 g
-  Connecting cable length: approx. 830 ��
-   Operating  and  storing  te�perature  range:  -10 °C 
up to +55 °C  (cli�ate category N)
-   Relati�e  air  hu�idity:  20 %  up  to  96 %  (cli�ate 
category N)
7.  General maintenance
Clean  the  exterior  of  the  housing  with  a  clean  dry 
cloth (exception: special cleansing cloths). Do not use 
solvents and/ or abrasives to clean the voltage tester.
8.   Environmental  notice
At the end of the product’s useful life, please 
dispose  of  it  at  appropriate  collection  points 
pro�ided in your country.