Chauvin Arnoux C.A 740N Voltage Tester P01191741Z Data Sheet

Product codes
P01191741Z
Page of 84
24
AUT
O TEST
Position beyond which your hands must not go.
 
„ If every third indicator is off, there is a problem with the 
leads. Check that they are correctly connected and that 
they are actually touching, then press the 
AUTO TEST  
button again. If the problem persists, the lead and/or the 
test probe must be replaced.
+
CAT IV
600V
400
230
127
50
690 AC
750 DC
12
24
+
-
ELV
Ph
COM
AC
DC
V
Ω
 
„ If no indicator lights, replace the batteries (see §4.2). If the 
problem persists with new batteries, the device is defective 
and must be sent in for repair (see §4.4).
After each check, perform a self-test in order to confirm the 
proper operation of the device.
In a noisy environment, make sure that you can in fact hear 
the audible signal emitted by the device.
Remark:  If the AUTO TEST button is kept pressed for 
more than 10 seconds when the test probes are 
not touching each other, the device switches to 
standby.
2.2. VOLTAGE DETECTION
Connect the red test probe to the 
+ terminal and the black 
lead to the 
COM terminal.
Keep your hands behind the guards of the device and of 
the test probe.
Place the test probes on the element to be tested and main-
tain a firm contact.
There is no need to switch the C.A 740N on, because it starts 
up automatically.