Eaton MMX34AA1D3F0-0 3-phase frequency inverter, to , 121397 121397 Data Sheet
Product codes
121397
03/10 AW
A
8230
-2416
14/14
Emergency On Call Service: Local representative (
http://www.moeller.net/address
) or +49 (0) 180 5 223822 (de, en)
Eaton Industries GmbH, Hein-Moeller-Straße 7-11, D-53115 Bonn
© 20
© 20
08 by Eaton Industries GmbH
Subject to
alterations
alterations
03/10 AWA8230-2416
DPD00190
Doku
Printed in PRC (03/10)
UL
®
Cautions, Warnings and Instructions
Wiring Warnings for Electrical Practices and Wire Sizes
The Cautions, Warnings, and instructions in this section summarize the
procedures necessary to ensure an inverter installation complies with
Underwriters Laboratories
procedures necessary to ensure an inverter installation complies with
Underwriters Laboratories
®
guidelines.
Circuit Breaker and Fuse Sizes
The adjustable frequency drive’s connections to input power must include
UL Listed inverse time circuit breakers with 600 V rating, or UL Listed fuses as
shown in the table below.
UL Listed inverse time circuit breakers with 600 V rating, or UL Listed fuses as
shown in the table below.
Terminal Tightening Torque and Wire Size
The wire size range and tightening torque for field wiring terminals are
presented in the table below.
presented in the table below.
Wire Connectors
Motor Overload Protection
MMX adjustable frequency drives provide solid-state motor overload protection,
which depends on the proper setting of the following parameter: P7.2 “current
limit“.
which depends on the proper setting of the following parameter: P7.2 “current
limit“.
Set the rated current [Amperes] of the motor(s) with the above parameters.
The setting range is 0.2 * rated current to 2 * rated current,
The setting range is 0.2 * rated current to 2 * rated current,
a manual
AWB8230-1603.
Warning!
Use 60/75 °C Cu wire only or equivalent.
Use 60/75 °C Cu wire only or equivalent.
Warning!
Open Type Equipment.
Open Type Equipment.
Warning!
Suitable for use on a circuit capable of delivering not more than
5,000 rms symmetrical amperes:
Suitable for use on a circuit capable of delivering not more than
5,000 rms symmetrical amperes:
• 120 V maximum for MMX11 models.
• 240 V maximum for MMX12 and MMX32 models.
• 480 V maximum for MMX34 models.
• 240 V maximum for MMX12 and MMX32 models.
• 480 V maximum for MMX34 models.
Warning!
Field wiring connections must be made by a UL Listed and CSA
Certified ring lug terminal connector sized for the wire gauge being
used. The connector must be fixed using the crimping tool specified
by the connector manufacturer.
Field wiring connections must be made by a UL Listed and CSA
Certified ring lug terminal connector sized for the wire gauge being
used. The connector must be fixed using the crimping tool specified
by the connector manufacturer.
Warning!
When two or more motors are connected to the inverter, they cannot
be protected by the electronic overload protection. Install an external
thermal relay on each motor.
When two or more motors are connected to the inverter, they cannot
be protected by the electronic overload protection. Install an external
thermal relay on each motor.
Terminal (ring lug)
Cable
Cable support
Cable
Cable
PE
Inverter Model
Input Voltage
Motor Output
1)
Fuse/Breaker
(UL-rated, class J, 600 V)
(UL-rated, class J, 600 V)
Wiring Size Range
Torque
kW
HP
A
AWG
ft-lbs
Nm
MMX11AA1D7
...
MMX11AA2D4
...
MMX11AA2D8
...
MMX11AA3D7...
115 V
Single Phase
Single Phase
0.25
0.37
0.55
0.75
0.37
0.55
0.75
L
M
O
1
1
20
14
0.44
0.6
MMX11AA4D8
...
1.1
1
M
30
10
MMX12AA1D7
...
MMX12AA2D4
...
MMX12AA2D8
...
230 V
Single Phase
Single Phase
0.25
0.37
0.55
0.37
0.55
L
M
O
10
16
0.44
0.6
MMX12AA3D7
...
MMX12AA4D8
...
MMX12AA7D0
...
0.75
1.1
1.5
1.1
1.5
1
1
1
M
2
20
14
MMX12AA9D6
...
2.2
3
30
10
MMX32AA1D7
...
MMX32AA2D4
...
MMX32AA2D8
...
MMX32AA3D7
...
230 V
Three Phase
Three Phase
0.25
0.37
0.55
0.75
0.37
0.55
0.75
L
M
O
1
1
6
16
MMX32AA4D8
...
1.1
1
M
10
16
MMX32AA7D0
...
MMX32AA9D6...
1.5
2.2
2.2
2
3
3
20
14
MMX34AA1D3
...
MMX34AA1D9
...
MMX34AA2D4
...
MMX34AA3D3
...
460 V
Three Phase
Three Phase
0.37
0.55
0.75
1.1
0.55
0.75
1.1
½
¾
1
1½
¾
1
1½
6
16
0.44
0.6
MMX34AA4D3
...
MMX34AA5D6
...
1.5
2.2
2.2
2
3
3
10
16
MMX34AA7D6
...
MMX34AA9D0
...
MMX34AA012
...
3
4
5.5
4
5.5
–
5
7½
5
7½
20
14
MMX34AA014
...
7.5
10
25
12
1) kW @ 230 V/400 V, 50 Hz, 1500 min
-1
HP @ 230 V/460 V 60 Hz, 1800 rpm
h
AWG = American Wire Gauge. Smaller numbers represent increasing wire thickness.
MCM/kcmil = 1,000 circular mils, a measure of wire cross-sectional area
mm
MCM/kcmil = 1,000 circular mils, a measure of wire cross-sectional area
mm
2
= square millimeters, a measure of wire cross-sectional area