Novatek THREE-PHASE POWER LIMITER OM-310 OM-310 Data Sheet

Product codes
OM-310
Page of 28
- 4 - 
ОМ-310
                                                                                                                                                       
NOVATEK-ELECTRO
 
1.1.3 Integrated relays output terminals specification 
The internal relays output terminals specifications are outlined in Table 1.1 and Table 1.2 
Table 1.1 - Load relay 
 
 
Max. current 
for U~ 250 V 
Number of trips 
х1000 
Max switching 
power 
Max sustained safe 
AC/DC voltage 
Max. current for 
U = 30V D.C. 
Cos 
ϕ  = 0.4 
Cos 
ϕ  = 1.0 
5 А 
8 А 
200 
100 
1000 V
А 
440/125 V 
1.3 А  
    
     Table 1.2  - Characterizing relay 
 
 
Max. current 
for U~ 250 V  
Number of trips 
х1000 
Max switching 
power 
Max sustained safe 
AC/DC voltage 
Max. current for 
U
пост = 30V D.C. 
Cos 
ϕ  = 0.4 
Cos 
ϕ  = 1.0 
5 А 
16 А 
400 
100 
4000 V
А 
440/125 V 
3 А 
 
1.1.4 List of abbreviations used 
AR – automatic reset 
M
С – magnetic contactor 
PC - personal computer 
CT – current transformer 
MMSP – mode with minimal number of setting parameters 
Itt -  rated current of CT. (Specified when external CTs are used. For example, if a CT of T type-0.66 300/5, then 
I
tt
 will equal 300
А) 
In -  rated current of load.  
 
1.2 TECHNICAL BRIEF 
1.2.1 Basic technical parameters are shown below in table 1.3 
 
  Table 1.3 - Basic Technical Parameters 
 
Rated supply voltage: Three-phase 380V 50Hz  
 
Mains frequency, Hz 
48-62 
Rated load wattage range (during operation with use of integrated current transformers), kW 
3-30 
Tripping threshold accuracy for wattage, % of rated wattage, at most 
Tripping threshold accuracy for current, % of rated current, at most 
Tripping threshold accuracy for voltage, V, at most  
Phase imbalance detection accuracy for voltage, V, at most  
Minimum operational voltage: 
-single-phase
 
voltage
 
power
 
supply
 
when
 
one
 
phase
 
and
 
neutral
 
wires
 
are
 
connected
,
 
V,
 
not
 
less
 
- three-phase power supply voltage, V, at most  
 
180 
450 
Analog inputs 
- remote switch connection input 
- three analog inputs for connecting standard CT with 5A output (of 
Т-0.66 type or similar) 
- input for connecting differential current transformer (zero sequence transformer) 
 
Main outputs 
   load relay – two groups of changeover contacts -
8A 250V cos φ=1; 
  characterizing relay – one group of changeover contacts -16A 25
0V at cos φ=1 (the relay 
function is assigned by the user); 
 
Power consumption (under load), VA, at most  
5,0 
Enclosure protection degree:                - frame 
                                                               - terminal block 
IP40 
IP20 
Climate zone version 
У3.1 (moderate) 
Operating  temperature range, °C 
from -35 to +55 
Storage temperature, °C 
from -45 to +70 
Weight, kg, at most 
0,5 
Case dimensions (diagram 1.1) - nine S-type modules 
Mounting onto standard 35 mm DIN-rail 
Mounting position any                                                   
 
 
1.2.2 Measured and calculated parameters output to the display unit, their effective range limits and toler-
ances are given below in Table 1.4. 
 
Note: The display device includes: 
 
- two pieces of three-digit, seven segment indicators on OM-310 front panel;