Advantech ADAM-6050 18-Channel Isolated Digital I/O Modbus TCP Module ADAM-6050-BE Data Sheet

Product codes
ADAM-6050-BE
Page of 1
www.advantech.com/products
Online Download
All product specifications are subject to change without notice 
Last updated : 20-Jan-2006
General
 
Channels 
12 DI, 6 DO
 
Digital Input 
  Dry Contact: 
Logic level 0: close to 
GND 
Logic level 1: open
  Wet Contact: 
Logic level 0: 3 V max 
Logic level 1: 10~30 V
DC
  Counter:  
Up to 3 kHz
  Frequency: 
0.3 ~ 3000 Hz max.
 
Digital Output 
Open Collector to 30 V 
200 mA max. load 
Pulse Output: Up to 
5 kHz
Ordering Information
 
ADAM-6050  
18-channel isolated  
Digital I/O module
18-channel Isolated Digital I/O Module
16-channel Isolated Digital I/O w/Counter Module
16-channel Source Type Digital I/O Module
General
 
Channels 
12 DI, 2 DO, 2 Counter
 
Counter
  Maximum Count:  
4,294,967,285(32 bit)
  Input frequency:  
0.3 ~ 4500 Hz max. 
(frequency mode) 
4500 Hz max. 
 (counter mode)
  Isolation voltage:  
2000 V
RMS
  Modes:  
Counter, Frequency
 
Digital Input 
  Dry Contact: 
Logic level 0: close to 
GND 
Logic level 1: open
  Wet Contact: 
Logic level 0 : +3 V max 
Logic level 1 : +10 V to 
30 V
DC
  Counter: 
Up to 4.5 kHz
  Frequency: 
Up to 3 kHz
 
Digital Output 
Open Collector to 30 V 
200 mA max. load 
Pulse Output: up to 
5 kHz
Ordering Information
 
ADAM-6051 
16-channel isolated 
Digital I/O with counter 
module
General
 
Channels 
8 DI, 8 DO
  Digital Input
  Dry Contact: 
Logic level 0: close to 
GND 
Logic level 1: open
  Wet Contact: 
Logic level 0 : +3 V max 
Logic level 1 : +10 V to 
30 V
DC
  Digital Output: 
V
DC
: 35 V
  (Source Type) 
Current: 1 A 
Ordering Information
 
ADAM-6052 
16-channel Source Type 
Digital I/O module
ADAM-6050
ADAM-6051
ADAM-6052
ADAM-6050
ADAM-6051
ADAM-6052
Specifications
Specifications
Specifications
Common Specifications
General
 
Certifications 
CE, FCC class A
 
Dimensions (WxHxD)  70 x 112 x 25 mm
 
Connectors 
1 x RJ-45 (LAN) 
Plug-in screw terminal 
block (I/O, and power)
 
Enclosure 
ABS+PC
 
LAN 
10/100Base-T
 
LED Indicators 
Power and 
communication 
 
Mounting 
DIN 35 rail, stack, wall
 
Power Consumption 
2 W (typical) 
 
Power Input 
Unregulated 10~30 V
DC
Protection
 
 
Power Reversal Protection
 
Optical Isolation 
2,000 V
RMS
Environment
 
Humidity (Operating)  20 ~ 95% RH 
(non-condensing)
 
Humidity (Storage) 
0 ~ 95% RH 
(non-condensing)
 
Operating Temperature  -10 ~ 70° C
 