Lappkabel 2170232 Interface Cable 2 x 1.5 mm² Red 2170232 Data Sheet

Product codes
2170232
Page of 1
U.I. Lapp 
GmbH 
DATA SHEET 
 
 
 
    
 
UNITRONIC BUS AS-INTERFACE (TPE)
 
 
DB2170230                   
valid from: 16.05.2012 
 
Originator: RAWE/PDC 
approved: HAPF/PDC
 
Document: 
DB2170230 
page 1 of 1 
All rights reserved acc. to DIN ISO 16016. 
PD 0019/2.2_11.10DE 
Application  
Field bus cable for AS-Interface (actuator-sensor interface) networking system for the lower field area. Data transmission for 
AS-Interface telegrams and power supply for AS-I slaves, master, repeater, extender and sensors is done via this un-
screened, geometrically-coded two-core flat cable. The contacting of the conductors by the insulation-displacement-system 
of the AS-I modules is possible without stripping the insulation. 
 
The oil-resistant outer sheath of this field bus cable recommends its use in typical industrial environment, especially in wet 
areas of automotive industry and machining centers in combination with water-based and water-mixable cooling lubricants. 
The cable is intended for flexible application and permanent installation in dry and damp interiors.  
Design 
Conductor  
tinned copper, fine-wire stranded, nom. 1.5 mm
2
 acc. to IEC 60228/VDE 0295 
(class 6)  
Insulation 
oil resistant TPE, core  nom. 2.5 mm 
Core identification code 
cores brown and blue 
Core assembly 
2 cores parallel deviation, the brown core is assembled inline with the leading 
edge 
Outer sheath 
oil resistant TPE, yellow similar to RAL1021 (article number 2170230), black 
similar to RAL 9005 (article number 2170231) or red similar to RAL 3000 (article 
number 2170232) 
Electrical properties at 20° C 
Resistance (loop)  
max. 27.4 Ω/km 
Insulation resistance 
min. 10 GΩxcm 
Mutual capacitance 
max. 80 nF/km 
Inductance 
0.5 mH/km up to 0.75 mH/km 
Characteristic impedance 
70 Ω up to 140 Ω 
(at 167 kHz) 
Operating voltage 
ca. 30 V (DC) 
(230 V (AC) for the red version) 
Operating peak voltage 
300 V (not for power purposes) 
Test voltage U
eff.
 core/core  
2000 V 
Mechanical and thermal properties 
Minimum bending radius 
moved: 16 mm in center line 
  static: 12 mm in center line 
Permissible temperature range 
moved: -30˚ C up to +85˚ C 
  static: -40˚ C up to +85˚ C 
Halogen free 
acc. to VDE 0472-815 
General requirements 
Dangerous and forbidden substances acc. to RoHS directive (2002/95/EG) are 
not allowed to the manufacturing.