Requirements for the distance between Ethernet cable and other pipelines are shown 
 
in the table.
Other Pipelines
Ethernet Cable
Min Parallel Net Length 
L (mm1
Min Parallel-overlapping Net Height 
H (mm1
Down-conductor
1000
300
PE
50
20
Service pipe
150
20
Compressed air pipe
150
20
Thermal pipe (not wrapped1 500
500
Thermal pipe (wrapped1
300
300
Gas pipe
300
20
The two diagrams below demonstrate parallel net length and parallel-overlapping net 
height.
Note: The above minimum net length/height is required when metal raceway is not 
used. If any requirements cannot be met, you can add a steel tube or metal raceway 
for shielding.
Requirements  for  the  distance  between  Ethernet  cable  and  high-power  electric 
 
devices are in following tables.
Cable
Pave Way
Min Parallel 
Length (mm1
<2kVA 
powerline
Parallel cabling
130
One is in the grounded metal raceway or metal pipe
70
The both are in the grounded metal raceway or metal pipe
10
2~5kVA 
powerline
Parallel cabling
300
One is in the grounded metal raceway or metal pipe
150
The both are in the grounded metal raceway or metal pipe
80
>5kVA 
powerline
Parallel cabling
600
One is in the grounded metal raceway or metal pipe
300
The both are in the grounded metal raceway or metal pipe
150
Device
Min Distance (m1
Switch case
1.00
Transformer room
2.00
Elevator tower
2.00
Air-conditioner room
2.00
Lightning Protection