Honeywell evohome Thermal actuator, passive (NC) MT4-230-NC Data Sheet

Product codes
MT4-230-NC
Page of 5
MT SMALL LINEAR THERMOELECTRIC ACTUATORS
 
EN0B-0490GE51 R0106 
3
ELECTRICAL SPECIFICATIONS 
Table 3. Electrical specifications 
runtime for full nominal valve stroke 
order number 
initial 
current* 
permanent 
current* 
power 
consumption* 
4 mm models 
8 mm models 
MTx-024-xx, MTx-024S-xx 
~0.7 A 
< 0.1 A 
< 3 W 
4.0 min 
6.0 min 
MTx-024LC-xx 
~0.2 A 
< 0.05 A 
< 2 W 
6.0 min 
7.5 min 
MTx-230-xx, MTx-230S-xx 
~0.6 A** 
0.014 A 
3 W 
2.5 min 
3.5 min 
MTx-230LC-xx 
~0.4 A** 
0.010 A 
2 W 
3.5 min 
5.5 min 
*All values at nominal voltage. **Average during first 500 msec. 
 
MOUNTING 
NOTE:  Connection leads must not touch piping (heat 
transfer). 
Klick
IP44
IP44
IP44
 
Fig. 1. Mounting / installation positions 
or
 
Fig. 2. Dismounting 
FUNCTION 
When the operating current is applied, a PTC resistor heats 
up a wax element. After a delay, this wax element expands, 
causing stroke movement.