Yuasa NPL 78-12, 12V Ah lead acid battery YUANPL78-12IFR YUANPL78-12IFR Data Sheet

Product codes
YUANPL78-12IFR
Page of 2
NPL78-12
IFR
General Specifications
NPL Valve Regulated 
Lead-acid Batteries (VRLA)
The NPL range is an enhanced NP design
resulting in a longer service life (7 - 10yrs). All
other attributes and operational characteristics
are the same, thereby maintaining the benefit
of a common mechanical and electrical design
for users of both products.
FEATURES
Yuasa VRLA batteries can be used in any orientation excluding continuous use inverted.
Standard case material is flame retardant to (UL94) HBØ.
FR option case material is flame retardant to UL94:VØ (oxygen index 30).
NPL batteries are manufactured in factories that comply with ISO 9001:2000.
FR option NPLs comply with BS6290 Part 4 (1997).
NPL batteries comply with IEC 60896-21+22.
Nominal Capacity (Ah)
20hr to 1.75vpc
20°C
10hr to 1.75vpc
20°C
5hr to 1.70vpc
20°C
1hr to 1.60vpc
20°C
Voltage
Energy Density (Wh/L)
Specific Energy (Wh. kg)
Int Resistance (m.ohms)
Maximum discharge (A)
Short Circuit current
Dimensions (mm) +/- 2mm
Length
Width
Height overall
Weight 
Terminal
Torque (Nm)
Operational Temperature Range
Charge
-15°C to 50°C
Discharge
-20°C to 60°C
Storage
-20°C to 50°C (fully charged condition)
Applications
• Security and Fire  • UPS
• Telecoms  • Emergency Lighting
Terminals
Layout
NPL
78
72.6
66.3
46.8
12
85
34
<5
500
800
380
166
174
27.5
D
6.1
Terminal
x
y
D:
20mm
M8
www.yuasa-battery.co.uk
D
Da
atta
a  S
Sh
he
ee
ett
NPL SERIES - N
NP
PL
L7
78
8--1
12
2
IF
FR
R
NPL78-12*
*Model available in
Flame Retardent
case only.