Hobart Corp. Water System WS-40 User Manual

Page of 10
DISC SELECTION
DISC SELECTION WS-40/80
 
The amount of hardness removed (in compensated gpg) will be based on the amount of brine and the meter disc
selected.
1.
Determine the compensated hardness. This requires a hardness test and an iron test on raw water at the
application site. Compensated hardness is calculated by multiplying the ferrous iron (in ppm) by 3 and adding
it to the grains of hardness.
2.
To test the water supply, use the water analysis test kit available through Pro Products Inc. The recommended
kit is #2401 Field Analysis Kit. To order the test kit contact Pro Products at 800-285-9176 or visit
www.ProProducts.com.
3.
Determine the salt setting. The salt setting is determined by taking the compensated hardness (calculated in
step 1 above) and using the specification table for model WS-40 or WS-80.
4.
Verify the float cup setting. Use specifications for the WS-40 or WS-80 to determine the correct setting the
float cup height.
 
Specifications
WS-40
WS-80
Salt usage / generation
1.0 lbs.
1.4 lbs.
Capacity
2,527 grains
4,818 grains
Efficiency
2,527 gr./lb.
3,442 gr./lb.
Dosing
5.5 lbs./cu. ft.
3.5 lbs./cu. ft.
Float cup setting
6.25"
6.5"
 
Disc Number
1
2
3
4
5
6
7
8
4
8
11
15
19
23
27
30
Gallons Between
Regeneration
9.1
9.1
9.1
9.1
8.4
6.6
5.4
4.4
Rregeneration Gallons
(min.) @ 15 psig
583
282
194
146
117
97
83
73
*   Compensated hardness in gpg = Hardness + (3 x Fe in mg/l)
 
Disc Number
1
2
3
4
5
6
7
8
5
11
17
22
27
32
35
40
Gallons Between
Regeneration
10.2
10.2
10.2
10.2
10.2
8.3
6.7
5.5
Rregeneration Gallons
(min.) @ 15 psig
732
366
244
183
146
122
105
92
*   Compensated hardness in gpg = Hardness + (3 x Fe in mg/l)
 
WS-40/80 Hobart Compact Water Softener Installation Instructions - DISC SELECTION
F25404 Rev. A (0413)
Page 10 of 10