10.4 Stand-alone
operation
In the stand-alone mode the transponder operates with no need of any further connections to
a fire alarm system. To connect local arm devices the relay common fire (Sa-Feu) and/or
common fault (Sa-Stör) may be used.
a fire alarm system. To connect local arm devices the relay common fire (Sa-Feu) and/or
common fault (Sa-Stör) may be used.
A fault message may be transmitted via the common fault relay to, e.g. a supervising system
or an authorized person.
or an authorized person.
Reset
To reset the transponder connect an external reset button (refer to
c) or a relay contact. In
this case a voltage of 9 to 30 V DC must be switched for at least 1 second at the input (input +/-)
of the IQ8Wireless transponder.
of the IQ8Wireless transponder.
-
+
9 V DC - 30 V DC
Reset
J1
J2
C
NO
NC
C
NC
NO
R
-
+
Eing
-
+
U
B
P
1
Jumper J1 + J2
removed
removed
-
+
-
IN OUT
+
Sa-Feuer
Common fire
Sa-Stör
Common fault
Fig. 21: Required wiring for the stand–alone operation
Connection data
•
External power supply 9 V DC to 30 V DC
•
Jumper J1 and J2 removed
•
Reset time = 0.2 to 3 seconds